Installation: Mechanical
36" (914 mm)
Recommended
clearance
Height
Width
18" (457 mm)
Recommended
clearance
CL1/CL2
Length
CL1/CL2
48" (1219 mm)
Recommended
clearance
Table 7. Dimensions for figure 13
Clearance Tube Pull
Feet-Inch (mm)
Compressor
Shell Size
CL1
CL2
Length
Height
Width
400-500
500
13' 11"
3' 7"
13' 5"
6' 11"
6' 6"
(4.235)
(1.092)
(4.083)
(1.790)
(1.984)
560-700
700
13' 11"
3' 7"
13' 5"
6' 11"
6' 10"
(4.235)
(1.092)
(4.083)
(1.790)
(2.083)
740-1000
1000
13' 11"
3' 7"
13' 5"
8' 4"
7' 6-3/4"
(4.235)
(1.092)
(4.083)
(2.540)
(2.305)
Notes:
CL1 at either end of the machine and is required for tube pull clearance.
CL2 is always at the opposite end of the machine from CL1 and is required for service clearance.
Add 14-5/8" (37.1 cm) on each end for the water box.
Unit Dimensions With Unit
Mounted Starters
Figure 13. Recommended operating and service clearances –
Model CVGF with unit-mounted starters
Dimensions Feet-Inch (m-meters)
CVGF-SVX03B-EN
48
Summary of Contents for CVGF1000
Page 6: ...TRMM Tracer Communications UCP Unit Control Panel CVGF SVX03B EN 6 General Information...
Page 125: ......
Page 126: ......
Page 127: ......