General Requirements
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electri-
cian or other individual who has been properly trained in handling live electrical com-
ponents perform these tasks. Failure to follow all electrical safety precautions when
exposed to live electrical components could result in death or serious injury.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be
necessary to measure the speed of rotating components. Have a qualified or licensed
service individual who has been properly trained in handling exposed rotating com-
ponents, perform these tasks. Failure to follow all safety precautions when exposed to
rotating components could result in death or serious injury.
As you review this manual, along with the wiring instructions presented in this sec-
tion, keep in mind that:
All field-installed wiring must conform to National Electric Code (NEC) guidelines, as
well as to any applicable state and local codes. Be sure to satisfy proper equipment
grounding requirements per NEC.
All field-installed wiring must be checked for proper terminations, and for possible
shorts or grounds.
Do not modify or cut enclosure to provide electrical access. Removable panels have
been provided for this purpose. Modify these panels only; away from enclosure. Refer
to installation information shipped with the starter or submittal drawings.
CAUTION
TO AVOID DAMAGE TO STARTER COMPONENTS,
remove debris inside the starter panel. Failure to do so may cause an electrical short
that seriously damages the starter components.
Power Supply Wiring
To assure that power supply wiring to the starter panel is properly installed and con-
nected, review and follow the guidelines outlined below.
3-Phase Power Source
1. Verify that the starter nameplate ratings are compatible with the power supply char-
acteristics and with the electrical data on the unit nameplate.
2. If the starter enclosure must be cut to provide electrical access, exercise care to pre-
vent debris from falling inside the enclosure. If the starter cabinet has a removable
panel, be sure to remove the panel from the unit before drilling holes.
CAUTION
Damage to Starter components!
To avoid damage remove debris inside the starter panel. Failure to do so may cause
an electrical short that seriously damages the starter components.
Installation: Electrical
CVGF-SVX03B-EN
76