CVGF-SVU02B-E4
32
Unit Control
Panel (UCP)
The
active chilled water setpoint
is the setpoint that is currently in
use. It will be displayed to 0.1
degrees Fahrenheit or Celsius.
Touching
the double arrow
to
the left of the Active Chilled
Water Setpoint will take the user
to the active chilled water
setpoint arbitration sub-screen.
The
Active Chilled Water
Setpoint
the result of arbitration
between the front panel, BAS,
and external setpoints.
The
chilled water reset status,
in
the right most column, will
display one of the following
messages: Return, Constant
Return, Outdoor, None
The left column text “Front
Panel”, “BAS”, “External”,
Chilled Water Reset, and “Active
Chilled Water Setpoint” will
always be present regardless of
installation or enabling those
optional items. In the second
column “- - - -” will be shown if
that option is Not Installed,
otherwise the current setpoint
from that source will be shown.
The
“Back” button
provides
navigation back to the chiller
screen.