NOTE:

 

On the 

Charge Assist™ control 

set the LINE LENGTH 

DIP SWITCHES before running system or entering 

CA Mode.  

See Subcool Charging Corrections Table on page 2. 

The Communicating Comfort Control will auto-configure the 
system size and airflow requirement at power-up.  The Charge 
Assist™ (CA) Mode will set the indoor blower to 100%, over-
ride any blower delays and run compressor 2nd stage.  (Green 
LEDs 

Y1

 and 

Y2

 will be on.  The Green 

Status 

LED will be 

turned off.)

Procedure 

STEP 1:

   

 Press 

MODE

 button (See Figure 2) for 2 seconds to enter 

the 

CA

 mode.  The 

CA

 control takes control of the system 

and overrides the Communicating Comfort Control.  The 

Green STATUS  

LED is turned OFF.  The 

CA

 control will 

run the first stage compressor for one minute.  Green LED 
Y1 is on.  The CA control will then run the second stage 
compressor.  Green LEDs Y1 and Y2 will then be ON.  The 

CA

 control now starts its Charge Assist™ mode. The 

CA

 

control will now check the operating Conditions before 
continuing the 

CA

 Mode.

NOTE:

 

 To stop the 

CA

 mode at anytime, press the 

MODE

 

button.  The 

CA

 control will then begin slowly flashing its 

Green

 STATUS  

LED indicating that the 

CA

 control is now 

in its normal operating mode.

Outdoor Temperature

 (

ODT

) Must be between 55°F and 

120°F. If 

ODT

 is below 55°F or above 120°F, the 

ODT

OUT OF RANGE

, Red LED will flash ON and OFF for 30 

seconds.  This error condition causes the 

CHARGING

  

(STABILIZING) Amber LED to flash 10 times.  The 

CA

 

control will then exit the 

CA

 mode and the Green

 Status 

LED begins to flash slowly.

Liquid Line Temperature 

(Must be within range) If this 

sensor is shorted or open - This error condition causes an 
11 flash on 

FAULT

 LED.

Liquid Line Pressure 

(Must be above 90 psig) If the liquid 

pressure is below 90 psig, the 

LOW

 

PRESSURE

 Red LED 

will turn on for 30 seconds.  This error condition causes the 

CA

 control to flash its 

CHARGING

 

(STABILIZING) 

Amber 

LED 10 times.  The 

CA

 control will then exit the 

CA

 mode 

and it then begins flashing its Green

 Status 

LED slowly.

STEP 2:

Enter Stabilization Routine

 The 

CHARGING

 (STABILIZ-

ING) 

Amber LED

 will begin to flash.

The 

CA 

control will then indicate the time it will take for the 

refrigerant system to stabilize by flashing its 

CHARGING

 

(STABILIZING) 

Amber LED.

  (See SUMMARY on page 7 

for flash rate details.)

The 

CA

 control may run the system for up to twenty min-

utes to insure the refrigerant system is at a steady operat-
ing state.  Once the system is at a steady operating state 
the 

CA

 control will enter the 

Charging Routine.

STEP 3: 

Charge Assist™ (CA) Procedure with a  Communicating Comfort Control 

CONTAINS REFRIGERANT!

SYSTEM CONTAINS OIL AND REFRIGERANT UNDER 

HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE 

PRESSURE BEFORE OPENING SYSTEM.
Failure to follow proper procedures can result in personal

illness or injury or severe equipment damage.

CAUTION

!

WARNING

!

Live Electrical Components!

During installation, testing, servicing and troubleshooting of 
this product, it may be necessary to work with live electrical 
components.  Failure to follow all electrical safety precautions 
when exposed to live electrical components could result in 
death or serious injury.

2

 

CHARGE ASSIST

TM

  CIRCUIT BOARD DETAIL

1

 

CHARGE ASSIST

TM

 

PORT LOCATION

LIQUID

REFRIGERANT

Summary of Contents for ComfortLink II 4TWZ0036B1000A

Page 1: ...Y R 410A REFRIGERANT AND APPROVED POE AB COMPRESSOR OIL PRODUCT SPECIFICATIONS OUTDOOR UNIT 12 POWER CONNS V PH HZ 3 MIN BRCH CIR AMPACITY BR CIR PROT RTG MAX AMPS COMPRESSOR NO USED NO SPEEDS VOLTS P...

Page 2: ...an be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 SCHEMATIC DIAGRAM MANUAL CHARGING BELOW 55 F OD AMBIENT IN HEATING MODE HP MODELS ONLY 1 The only r...

Page 3: ...2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system charge per these inst...

Page 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Page 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Page 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Page 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Page 8: ...0 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 150 160 5 5 15 25...

Page 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle NOTE 1 Line Dampener DO NOT REMOVE LINE DAMPENER SEE NOTE 1 LINE DAMPENER SEE NOTE 1 Printed from D155727P01 Rev03 9 REFRIGERATION CIRCUITS...

Page 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Page 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Page 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Page 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Page 14: ...g LPCO may trip Note The Close Valve Test will exit after 1 5 minutes 90 seconds and will not reinitiate requires a break and make to initialize To clear faults stored in memory apply a jumper between...

Page 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Page 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Reviews: