26
CLCH-SVX03C-EN
Installation - Mechanical
Module-to-Module Assembly
M-Series air handlers ship with all necessary assembly hardware and gasket material. The
hardware should be packaged in either a clear plastic envelope or cardboard box inside the fan
module, access module, or mixing box module.
The number of modules to be assembled often makes it necessary to use more than one module
to ship the assembly material; therefore, check all modules thoroughly before contacting your
Trane sales representative to report missing items.
Modules are joined with gasketing applied to one of the mating surfaces and hardware to bolt the
modules together. The gasketing for module-to-module joints is a closed cell foam with adhesive
backing.
WARNING
Heavy Objects!
Always place, assemble, and suspend modules/subassemblies one at a time. Placing,
assembling, and/or suspending more than one module/subassembly at a time may result in
death, serious injury, or equipment damage.
To assemble M-Series units:
1.
Locate the mounting hardware and gasket material.
2. Remove any shipping bolts located on the mounting surfaces of the modules (see
Figure 14
).
3. Apply the gasketing to one of the mating surfaces; see the following figures:
Figure 13. Module-to-module quick connect
If unit ships in multiple shipping splits, fasten
the quick connects where the modules bolt
together (
Figure 13
).