background image

Disassembly

12

 CVHM-SVN001C-EN

Important:

Any unit pressure must be relieved before 
disconnecting refrigerant lines. The units 
ship from the factory with a 5 psi dry 
nitrogen holding charge.

3. Disconnect the AFD cooling lines at the bottom of the 

elbows coming out of the chill plate, both feed and 
return. Cap the lines and chill plate elbows to prevent 
debris from entering the system.

4. Mark and disconnect the motor power wires at the 

drive output terminals and inside motor junction box. 
There will be six power wires and two ground wires.

Note:

Always compare the wire connections to the 
as-built wiring diagrams to assure the 
schematics match the actual connections. Make 
notes as necessary to assure the wires are 
reconnected to the same locations.

5. Remove wire tray covers and completely remove wires 

from wire tray. Disassemble and remove the wire tray 
by unbolting the tray at the compressor junction box 
and then removing the screws from support bracket on 
the AFD cabinet.

6. Mark and disconnect the high pressure cutout switch 

wires at the terminal block and pull the cable out of the 
AFD cabinet.

7. Mark and disconnect the wires that run between the 

drive and the control panel at the drive and pull the 
conduit out of the AFD cabinet.

8. Mark and disconnect the oil/refrigerant pump wires 

from the terminal block and pull conduit out of the AFD 
cabinet.

9. Mark and disconnect drive communication cable at 

terminal block and pull the cable out of the AFD 
cabinet.

10. Support the weight of the AFD cabinet with a fork truck 

or another suitable lifting device (minimum 2-ton rated 
capacity).

11. Loosen and remove the bolts that secure the AFD 

cabinet to the lower mounting brackets. Unhook the 
right side at the L-bracket welded to the condenser, four 
bolts total. Unhook the left side at the condenser 
support leg, four bolts and nuts total.

12. Carefully lift the AFD cabinet away from the chiller. Do 

not bump or jolt the AFD while lifting.

Important:

In cases where the unit is being installed 
through restricted spaces, the oil tank filter 
may need to be temporarily removed. Prior 
to removal of the filter, switch the regulator 
to the “change filter” setting. After the filter 
has been removed from the regulator block, 
the opening must be sealed to ensure no 
contaminates are allowed into the system. 
Due to the hygroscopic nature of the oil, 
install a new filter after the chiller has 
passed through the restricted space.

Installation of the AFD cabinet is essentially the reverse of 
the removal procedure. All mounting bolts should be 
torqued to ANSI standards based on the bolt diameter. The 
motor power wires connecting to the drive output 
terminals should be torqued according to the label inside 
the AFD cabinet. Tighten the power wires that connect to 
the AFD terminal block to 8.3 ft-lb (11.3 N-m). The motor 
powers wires connecting to the motor terminals inside the 
compressor motor junction box shall be torqued between 
20–26 ft·lb. Torque the corresponding ground cables 
inside the compressor motor junction box to 38 ft·lb. Refer 
to the as-built wiring diagrams for connection locations.

Purge Unit Removal

To remove the purge assembly from the top of the 
condenser:

1. Isolate the purge unit from the condenser shell by 

closing the vapor and liquid line valves.

WARNING

Refrigerant under Positive Pressure!

Failure to follow instructions below could result in an 
explosion which could result in death or serious injury 
or equipment damage. System contains oil and 
refrigerant and may be under positive pressure. 
Recover refrigerant to relieve pressure before opening 
the system. See unit nameplate for refrigerant type. Do 
not use non-approved refrigerants, refrigerant 
substitutes, or refrigerant additives.

WARNING

Refrigerant under Positive Pressure!

Failure to follow instructions below could result in an 
explosion which could result in death or serious injury 
or equipment damage. System contains oil and 
refrigerant and may be under positive pressure. 
Recover refrigerant to relieve pressure before opening 
the system. See unit nameplate for refrigerant type. Do 
not use non-approved refrigerants, refrigerant 
substitutes, or refrigerant additives.

WARNING

Hazardous Voltage w/Capacitors!

Disconnect all electric power, including remote 
disconnects and discharge all motor start/run 
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be 
inadvertently energized. Verify with an appropriate 
voltmeter that all capacitors have discharged. Failure to 
disconnect power and discharge capacitors before 
servicing could result in death or serious injury. 

For additional information regarding the safe discharge 
of capacitors, see PROD-SVB06A-EN

Summary of Contents for CenTraVac CVHM

Page 1: ...stallation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to th...

Page 2: ...y hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be performed by qualified pers...

Page 3: ... Trane products Trane or an agent of Trane specifically authorized to perform start up and warranty of Trane products will provide qualified personnel and standard hand tools to perform the disassembly and reassembly work at a location specified by the contractor The contractor shall provide the rigging equipment such as chain falls gantries cranes forklifts etc necessary for the disassembly and r...

Page 4: ...r in part without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the trademarks of their respective owners Revision History Updated information for AFD drive ...

Page 5: ...10 Contractor Responsibilities 10 Wiring Disassembly 11 Adaptive Frequency Drive Removal 11 Purge Unit Removal 12 Control Panel Removal 13 Tracer AdaptiView Display Arm Removal 14 Compressor Motor Assembly Removal 14 Economizer Removal 17 Condenser Evaporator Disassembly 18 Reassembly 19 Tightening Flanges 20 Brazing 21 Final Installation Procedures 21 ...

Page 6: ... are metric except waterbox and oil system hardware Note Use only new O rings and gaskets Do NOT reuse O rings or gaskets Components Figure 1 CVHM components page 1 of 2 Detail A Motor Cooling Return Tube Motor Casting Compressor Base Condenser Evaporator Economizer ...

Page 7: ...Weights CVHM SVN001C EN 7 Figure 1 CVHM components page 2 of 2 1st Volute Discharge 2nd Volute Discharge Wrap Around Pipe See Detail A Condenser Discharge Connection Drive Removed for Clarity Drive Removed for Clarity ...

Page 8: ...oles on the top of the drive can be used for lifting the drive Figure 2 CVHM drive dimensions in 56 5 8 15 11 16 5 5 8 22 1 7 8 CENTER OF GRAVITY 26 TO 31 CENTER OF GRAVITY 10 TO 12 72 5 16 1 11 16 51 5 16 6 1 8 39 1 3 8 1 3 4 35 7 16 34 1 16 5 8 13 16 ...

Page 9: ...re required for lifting the compressor assembly metric threads Note Wrap pipe requires three 5 8 in shackles Trane recommends using Crosby screw pin shackles model S 209 stock number 1018482 with 5 8 in pin Table 1 Maximum CVHM unit component weights Component Maximum Weight lb kg Condenser without waterboxes 4253 1934 Condenser waterboxes 923 420 Evaporator without waterboxes 6095 2771 Evaporator...

Page 10: ...ing refrigerants or oils could result in equipment damage including bearing damage introduction of acids into the chiller or continuous purge pump out in high head high ambient applications CenTraVac chillers are manufactured with different refrigerant oil systems R 123 chillers using OIL00022 and R 514A chillers using OIL00334 OIL00335 Verify proper refrigerant and oil for your chiller and do NOT...

Page 11: ...ed spaces or the AFD cabinet shipped disassembled from the chiller use the following general information and instructions The maximum weight of the drive is 1900 lb 862 kg Note For specific weights of the AFD cabinet refer to submittal package 1 Remove the AFD upper support bracket bolts at the wrap around pipe side There are two bolts in each bracket 2 Close the isolation valves for the AFD cooli...

Page 12: ...led to ensure no contaminates are allowed into the system Due to the hygroscopic nature of the oil install a new filter after the chiller has passed through the restricted space Installation of the AFD cabinet is essentially the reverse of the removal procedure All mounting bolts should be torquedtoANSIstandardsbased onthe boltdiameter The motor power wires connecting to the drive output terminals...

Page 13: ...ur bolts from the bottom of the panel which secure the panel to the lower mounting brackets 3 Loosen the two bolts on the back of the panel which secure the panel to the top mounting brackets See Figure 5 Figure 3 Purge unit Figure 4 Purge unit detail WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury...

Page 14: ...embling the chiller Cap or cover open lines to prevent entry of foreign material Figure 6 Control panel mounting brackets details WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing ...

Page 15: ...n shackle model S 209 stock number 1018482 with a 5 8 in pin is acceptable as shown in Figure 10 Figure 8 Lubrication system Figure 9 Lubrication system detail WARNING Heavy Objects Failure to follow instructions below or properly lift component could result in component dropping and possibly crushing operator technician which could result in death or serious injury and equipment or property only ...

Page 16: ...ve the two piece wrap pipe The wrap pipe can be disassembled at the mid flange joint a Lift the wrap pipe from the chiller being careful to avoid damaging flange surfaces b Install protective covers on the evaporator wrap pipe and compressor connections Plastic secured with duct tape makes an adequate cover if no heavy objects are set on the openings c Remove the second stage volute to condenser b...

Page 17: ...et it on a pallet Cover all openings to prevent the entry of foreign material into the economizer condenser and compressor 10 Use the reverse order to reassemble the economizer on the chiller Be sure to install new O rings at the appropriate joints NOTICE Handle with Care Failure to follow instructions below could result in equipment damage The cast iron base of the compressor and the discharge fl...

Page 18: ...shell support see Figure 16 Then remove the bolts from the flanges connecting the shells 4 Reassemble the evaporator and condenser shells in the reverse order Note Install the top bolts first as these have limited clearance and act as dowel pins 5 Torque all bolts to specifications listed in Table 2 p 20 WARNING Heavy Objects Failure to follow instructions below or properly lift component could re...

Page 19: ... base plate to protect the bare metal Install two new roll pins into the compressor casting Align the pins into the compressor mounting base Insert the bolts in the compressor base and discharge flange connections 4 Tighten the compressor base and discharge flange bolts See Table 2 p 20 for bolt torque specifications 5 Remove the lifting equipment 6 Set up dial indicators on the compressor end of ...

Page 20: ...d 13 Torque all bolts to specifications listed in Table 2 14 Reconnect the previously cut compressor supply and return lines oil supply and return lines and the motor cooling lines using the factory supplied couplings Tightening Flanges Flanges with 8 or 12 Bolts Tighten all bolts to a snug tightness following the numerical sequence for the appropriate bolt pattern as shown below Repeat this seque...

Page 21: ...nstallation can proceed for unit piping wiring etc After installation has been completed fill out CTV ADF001 EN CenTraVac Installation Completion Check Sheet and Request for Trane Service to schedule the startup the chiller commissioning process can be completed by Trane or under the supervision of authorized Trane personnel Note CTV ADF001 EN is also included in the Forms section of CVHM SVX001 E...

Page 22: ......

Page 23: ......

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial and residential applications For more information please visit trane com or tranetechnologies com CVHM SVN001C EN 28 Aug 2020 Supersedes CVHM SVN001B EN Feb 2019 ...

Reviews: