Maintenance
AH-SVX008C-EN
43
Humidifier Inoperative
Note:
See humidifier manual for additional help.
a. Water supply has been turned off or not
connected.
Connect and/or turn on water supply.
b. Humidifier switch is in “Off” position.
Turn switch to “Auto/On” position.
c. Electrical connections are loose.
Tighten electrical connections.
d. Humidifier fuses are blown.
Check for overcurrent by the humidifier
electrodes. Drain water from tank and refill.
Replace fuses.
e. Relative humidity is above setpoint.
Adjust humidistat setpoint.
f. Yellow status LED is flashing.
Consult humidifier manual.
g. Water conductivity is too low.
Add a teaspoon of table salt to the water through
the top of the cylinder. Typically only required on
initial start-up.
Table 10. Troubleshooting methods (continued)
Symptom
Probable Cause
Recommendation