
Installation
AH-SVX008C-EN
35
remove the adjustment cap from end of the valve. Using a
5/16 in. Allen wrench, turn clockwise to increase pressure
or counterclockwise to lower the pressure.
NOTICE
Compressor Failure!
Do not exceed 20°F superheat. Exceeding this
temperature may cause failure of the compressor.
The normal control setting for the quench valve is 20°F
superheat (when there is no call for cooling). The valve is
factory set and no adjustment should be necessary. If
adjustment is required, remove adjustment cap from the
valve. Turn the adjusting stem clockwise to increase
superheat and counterclockwise to decrease the
superheat.
Summary of Contents for CeilAir CW
Page 51: ......