Table 8.
Refrigerant pressure/temperature settings
Refrigerant Pressure/Temperature Settings
Normal
Min.
Max.
Sub-cooling°F
10
5
20
Superheat°F
15
10
20
Design Condensing Temp.
@ 95°F Ambient
125
105
140
Suction Pressure (psig)-
R407C
70
55
85
Fan Cycling Control- Fan On
(psig)- R407C
320
240
340
Fan Speed Control (psig)-
R407C
320
-
-
Flooded HP Control Valve
(psig)- R407C
205
Installation
AH-SVX008C-EN
31
Saturated Refrigerant Pressure Tables
The following table shows the refrigerant pressures are
provided for reference for R407C refrigerant.
Table 9.
Refrigerant vapor tables
R407C Refrigerant
Temp.
(°F)
Pressure
(psig)
Saturated Evaporating Temperature
20
37.9
Dew Point
Saturated
Vapor
22
40.1
24
42.3
26
44.7
28
47.1
30
49.6
32
52.1
34
54.8
36
57.5
38
60.3
40
63.2
42
66.1
44
69.2
46
72.3
48
75.5
50
78.8
Saturated Evaporating Temperature
Bubble Point
Saturated
Vapor
95
209
100
225
105
242
110
260
115
279
120
298
125
319
130
341
135
363
140
387