Trane CAUC-C20 Installation Operation & Maintenance Download Page 29

29

System Start-Up

Sequence of Operation

Standard Model 20 through 60 Ton air cooled condensers
function as the outdoor condensing units for appropriately
sized split refrigeration systems. These units, operating in
conjunction with a matched indoor compressor/evaporator
configuration, provide refrigerant condensing for these sys-
tems down to a normal ambient temperature of 40 F. Opera-
tion to 0

o

F ambient is possible with the addition of externally

mounted low ambient dampers.

All condenser fans are direct drive, 26 inch propeller type.
They are driven by 1 HP thermally protected motors.

Condenser fan cycling is accomplished through interlocking
the fan operation with compressor operation (5K1 & 5K2),
liquid line pressure switches (4S11 & 4S12). When the low
ambient option is applied, ambient temperature thermostats
(1S36 & 1S37) are used to provide additional fan cycling
control. Table 5-1 lists the condenser fan sequencing data
and Figure 5-1 illustrates the condenser fan locations with
their respective fan and relay designators.

When wired properly, the unit will start and operate satisfac-
torily as long as the operating temperature is above the
minimum operating temperature listed in Table 5-2.

The condensing unit operation starts and stops automati-
cally when the cooling demand is initiated and terminated
by the cooling circuit interlock relays illustrated in
Figure 5-2.

The control components are mounted in the various areas
of the unit as illustrated in Figure 5-3.

Table 5-1

Condenser Fan Sequencing Data

Controlling

Fan

Fan

Fan

Device (3)

"ON"

"OFF"

Identification

Customer

Interlock

5K1

5K1

2B1, 2B2, 2B3 (1)

Circuit 1

Closed

Open

Customer

Interlock

5K2

5K2

2B4, 2B5, 2B6 (1)

Circuit 2

Closed

Open

Fan

1S36 (2)

Temperature 67.5

o

F

65

 

F

2B3 (1)

Switch

1S37 (2)

 67.5

o

F

65

 

F

2B6

Fan

4S11

Pressure

275 psig 155 psig

2B1 (1)

Switch

4S12

 

275 psig 155 psig

2B6

Notes:
1. Bold fan identifies fans used on 25, 30, 50 & 60 Ton
    units only.
2. 1S36 and 1S37 normally-closed contacts open on
    ambient temperature drop to 65

o

F. Contacts reclose

    on ambient temperature rise to 67.5

o

F.

3. Above data does not apply when units are interfaced
    with Trane Model CCAD package chillers. UCM for
    the CCAD unit commands fan control.

Low Ambient Damper Operation
Low Ambient Dampers are available as a factory installed
option or can be field-installed. Dampers are used to extend
the operation of these units from the standard operational
temperatures to a minimum of 0

o

F without hot gas bypass

or 10

o

F with hot gas bypass. (These values apply when

wind speed across the condenser coil is less than 5 m.p.h.).
If typical wind speeds are higher than 5 m.p.h., a wind
screen around the unit may be required. By restricting the
airflow across the condenser coils, saturated condensing
temperatures can be maintained as the ambient tempera-
tures change.

The low ambient damper actuator controls damper modula-
tion for each refrigerant circuit in response to saturated con-
densing temperature.

Low Ambient Thermostat Operation
In addition to the low ambient dampers on 25, 30, 50 & 60
Ton units, a low ambient thermostat is installed to further re-
strict the airflow across the condenser by cycling the 2B3
condenser fan on 25 & 30 Ton units plus 2B6 on 50 & 60
Ton units. The thermostat opens when the ambient tem-
perature approaches 65

o

F and closes at approximately

67.5

o

F.

Summary of Contents for CAUC-C20

Page 1: ...S Date October 2008 File No SV UN S S CAUC IOM 7 10 08 December 2001 s e d e s r e p u S TM Remote Air Cooled Condensers Models J and Later Design Sequence CAUC C20 CAUC C40 CAUC C25 CAUC C50 CAUC C3...

Page 2: ...ing the information within this manual and follow ing the instructions the risk of improper operation and or component damage will be minimized It is important that periodic maintenance be performed t...

Page 3: ...led Control Wiring 17 Refrigerant Piping 18 Liquid Lines 18 Liquid Line Components 18 Discharge Hot Gas Lines 18 Discharge Line Components 19 Making Refrigerant Connections 19 Brazing Procedures 19 Le...

Page 4: ...d just above the Mylar nameplate and a third nameplate is located on the inside of the control panel door When ordering replacement parts or requesting service be sure to refer to the specific model n...

Page 5: ...5 General Information Continued Unit Component Layout and Shipwith Locations 60 Ton Unit Illustrated...

Page 6: ...iate Trane office before installing or re pairing a damaged unit Unit Clearances Figure 3 1 illustrates the minimum operating and service clearances for either a single multiple or pit application The...

Page 7: ...7 Installation Continued Figure 3 1 Typical Installation Clearances for Single Multiple or Pit Applications...

Page 8: ...8 Figure 3 2 CAUC C20 Unit Dimensional Data Recommended Clearances...

Page 9: ...9 Figure 3 2 Continued CAUC C25 Unit Dimensional Data Recommended Clearances...

Page 10: ...10 Figure 3 2 Continued CAUC C30 Unit Dimensional Data Recommended Clearances...

Page 11: ...11 Figure 3 2 Continued CAUC C40 Unit Dimensional Data Recommended Clearances...

Page 12: ...12 Figure 3 2 Continued CAUC C50 Unit Dimensional Data Recommended Clearances...

Page 13: ...13 Figure 3 2 Continued CAUC C60 Unit Dimensional Data Recommended Clearances...

Page 14: ...g and Center of Gravity Data Location of Center of Shipping Gravity Unit Weight X Z Size Max Lbs In mm In mm C20 1348 41 1026 30 754 C25 1394 41 1031 30 762 C30 1585 41 1046 31 790 C40 2366 44 1115 43...

Page 15: ...y 2 Align the mounting holes in the base rail of the unit with the holes in the top of the appropriate isolator Refer to Figure 3 4 for the appropriate isolator for each load point 3 Install a 1 2 NC...

Page 16: ...the mounting surface Leveling the Unit Before tightening the mounting bolts level the unit carefully Use the unit base rail as a reference Level the unit to within 1 4 inch over its entire length Use...

Page 17: ...ssor unit Refer to the Refrigerant Piping section for recommended discharge line components and guide lines Install shutoff valves in the liquid line s to isolate the fil ter drier s for service Insta...

Page 18: ...e unit sheet metal for the refrigerant piping entrance into the unit Liquid Line Components Filter driers and valves expansion valves charging valves etc should be provided in the liquid lines just be...

Page 19: ...enter the system which will contaminate the re frigerant system 6 Apply heat evenly over the length and circumference of the joint to draw the brazing material into the joint by capillary action Remov...

Page 20: ...ection and re make as a new joint Retest for leaks after making re pairs 8 Open the liquid line service valve and the compressor discharge service valve Field Installed Power Wiring An overall dimensi...

Page 21: ...3 1 0 1 4 7 2 0 9 200 230 60 3 180 220 208 254 17 4 20 20 4 1 0 4 1 20 7 0 9 C40 460 60 3 416 508 7 7 15 15 4 1 0 1 8 9 0 0 9 575 60 3 520 635 6 15 15 4 1 0 1 4 7 2 0 9 200 230 60 3 180 220 208 254 25...

Page 22: ...RMER AND ANY OTHER LOAD RATED AT 1 AMP OR MORE Calculation 1 MCA MOP and RDE MCA 1 25 x LOAD 1 LOAD 2 LOAD 4 MOP 2 25 x LOAD 1 LOAD 2 LOAD 4 Select a fuse rating equal to the MOP value If the MOP valu...

Page 23: ...rol wir ing modifications must be made to the CAUC units Refer to Figure 3 7 and the field wiring diagram in the CCAD package chiller installation literature Follow the ap propriate procedure below fo...

Page 24: ...24 Figure 3 7 Typical Interface Connection Diagram for CCAD 20 through 60 Ton Package Chiller...

Page 25: ...25...

Page 26: ...tely 15 minutes This is referred to as a standing vacuum test where time versus pressure rise The maximum allowable rise over a 15 minute period is 200 microns If the pressure rise is greater than 200...

Page 27: ...vacuation Time vs Pressure Rise 200 400 600 800 1000 1200 1400 1600 10 0 10 20 30 40 50 60 70 80 90 TIME IN MINUTES PRESSURE IN MICRONS Continuously increasing pressure indicates the presence of leaks...

Page 28: ...rical Phasing Proper electrical phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Se quence Indicator and fo...

Page 29: ...dentification Customer Interlock 5K1 5K1 2B1 2B2 2B3 1 Circuit 1 Closed Open Customer Interlock 5K2 5K2 2B4 2B5 2B6 1 Circuit 2 Closed Open Fan 1S36 2 Temperature 67 5o F 65 F 2B3 1 Switch 1S37 2 67 5...

Page 30: ...power is applied 5 Check the condenser fans for proper rotation The direc tion of rotation is clockwise when viewed from the top of the unit All Fans are Rotating Backwards 1 Turn the field supplied d...

Page 31: ...cylinder to monitor the amount of refrigerant entering the system Refer to Table 5 3 for the recommended refrigerant capacities for the condensing unit The weight of refrigerant required for the liqui...

Page 32: ...r foot Table 5 5 Sample Operator s Maintenance Log Refrigerant Circuit 1 Refrigerant Circuit 2 Current Ambient Compr Suct Disch Liquid Super Sub Compr Suct Disch Liquid Super Sub Temp Oil Press Press...

Page 33: ...33 Blank...

Page 34: ...34 Figure 5 2 Typical Wiring Schematic for 20 through 60 Ton Units...

Page 35: ...35...

Page 36: ...36 Figure 5 3 Typical Control Panel Connections Diagram for 20 through 60 Ton Units...

Page 37: ...37...

Page 38: ...necessary Check the fan shaft bearings for wear Replace the bear ings as necessary Lubricate the supply fan bearings Refer to the equip ment manufacturer for their recommended greases Note Over lubri...

Page 39: ...brush and a sprayer either a garden pump up type or a high pressure sprayer A high quality detergent is also required suggested brands include SPREX A C OAKITE 161 OAKITE 166 and COILOX If the deterge...

Page 40: ...irement 26 L Leak testing a refrigerant system 20 Liquid Line Drier Refrigerant Requirements 32 See Figure 5 4 Liquid Line Filter Drier 18 Liquid Line Moisture Indicators 18 Liquid Line Solenoid Valve...

Page 41: ...tial start up warrantor will furnish a replace ment heat exchanger Warrantor s obligation and liabilities under this warranty are limited to furnishing replacement parts Warrantor shall not be obligat...

Page 42: ...42...

Page 43: ...43...

Page 44: ...44...

Reviews: