14
Installation (Continued)
Table 3-1
Typical Unit Weights & Point Loading Data
Operating
Unit Weight on Isolator @ Mounting Location
Unit
Weight
1
2
3
4
5
6
Size
AL
CU
AL
CU
AL
CU
AL
CU
AL
CU
AL
CU
AL
CU
C20
1146
1343
320
371
326
365
248
306
252
301
C25
1190
1393
329
378
337
381
259
315
265
319
C30
1302
1594
353
414
371
444
282
355
296
381
C40
2048
2379
363
406
347
392
349
404
334
389
335
401
320
387
C50
2280
2672
407
464
392
449
387
453
373
438
367
441
354
427
C60
2465
3036
433
515
420
505
417
511
405
501
401
507
389
497
Notes:
1. Mounting locations correlate with those shown in point loading illustration.
Figure 3-3
Rigging and Center-of-Gravity Data
Location of Center of
Shipping Gravity =
Unit
Weight
X
Z
Size
(Max. Lbs)
In
mm
In
mm
C20
1348
41
1026
30
754
C25
1394
41
1031
30
762
C30
1585
41
1046
31
790
C40
2366
44
1115
43
1097
C50
2664
56
1428
43
1100
C60
3010
57
1440
44
1107
L I F T I N G A N D M O V I N G I N S T R U C T I O N S !
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS
SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT
UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE
SAME LENGTH. ADJUST AS NECESSARY FOR EVEN
LEVEL LIFT.
USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER
TO INSTALLATION MANUAL OR NAMEPLATE FOR UNIT
WEIGHT. REFER TO INSTALLATION INSTRUCTIONS
LOCATED INSIDE CONTROL PANEL FOR FURTHER
RIGGING INFORMATION.
Summary of Contents for CAUC-C20
Page 8: ...8 Figure 3 2 CAUC C20 Unit Dimensional Data Recommended Clearances...
Page 9: ...9 Figure 3 2 Continued CAUC C25 Unit Dimensional Data Recommended Clearances...
Page 10: ...10 Figure 3 2 Continued CAUC C30 Unit Dimensional Data Recommended Clearances...
Page 11: ...11 Figure 3 2 Continued CAUC C40 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 Figure 3 2 Continued CAUC C50 Unit Dimensional Data Recommended Clearances...
Page 13: ...13 Figure 3 2 Continued CAUC C60 Unit Dimensional Data Recommended Clearances...
Page 24: ...24 Figure 3 7 Typical Interface Connection Diagram for CCAD 20 through 60 Ton Package Chiller...
Page 25: ...25...
Page 33: ...33 Blank...
Page 34: ...34 Figure 5 2 Typical Wiring Schematic for 20 through 60 Ton Units...
Page 35: ...35...
Page 36: ...36 Figure 5 3 Typical Control Panel Connections Diagram for 20 through 60 Ton Units...
Page 37: ...37...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...