background image

31

System Start-Up (Continued)

Low Ambient Damper Adjustment

(Factory or Field Installed)

When a unit is ordered with the low ambient option (i.e.,
Digit 11 is a “1” in the model number), a damper is factory
installed over the lead condenser fan for each refrigeration
circuit. Refer to the appropriate unit illustrated in Figure 5-1
for the damper locations.

For field installation, mount the dampers over the con-
denser fans at the locations shown in Figure 5-1 and con-
nect the actuator, controller, and sensor for each circuit.
(Refer to the Installation Instructions provided with each low
ambient damper kit.)

The controller has a factory default setpoint of 105

 

F. This

setpoint can be adjusted by installing a field supplied resis-
tor on 2TB34 in the low ambient control panel located in the
back of the main control panel. (See the low ambient wiring
diagram, that shipped with the unit or with the field kit, for
resistance values and installation location.)

Inspect the damper blades for proper alignment and opera-
tion. Dampers should be in the closed position during the
“Off” cycle. If adjustment is required;

1. Remove the sensor leads from the input terminals 6 and

7 for circuit #1 and/or 11 and 12 for circuit #2. (Controller
output signal will go to 0.0 VDC and the damper will drive
to the closed position.)

2. Loosen the damper shaft “Locking” set screws on the ac-

tuator

3. Firmly hold the damper blades in the closed position

4. Retighten the “Locking” set screws.

To check damper operation, jumper between the sensor in-
put terminals 6 and 7 and/or 11 and 12 (if applicable). Con-
troller output signal will go to 10 VDC and the damper will
drive to the full open position.

Charging the System

1. Verify that all discharge service valves and liquid line ser-

vice valves for each circuit is back seated.

2. Attach a set of service gauges onto the liquid line and

discharge line gauge ports for each circuit.

3. Charge liquid refrigerant into the liquid line of each refrig-

erant circuit with the required amount of R-22. Refriger-
ant should be charged into the system by weight.

Use an accurate scale or a charging cylinder to monitor
the amount of refrigerant entering the system. Refer to
Table 5-3 for the recommended refrigerant capacities for
the condensing unit. The weight of refrigerant required
for the liquid line and liquid line driers are listed in Table
5-4.

If the pressure within the system equalizes with the pres-
sure in the charging cylinder before charging is com-
pleted, complete the process by vapor charging into the
suction (low) side of the system after the system has
been started.

Table 5-2 gives the minimum starting temperatures for
both “Standard” & “Low” Ambient units.

Do not attempt to charge the system with the low ambi-
ent dampers and/or hot gas bypass operating (if appli-
cable). Disable the low ambient dampers in the “Open”
position (refer to the “Low Ambient Damper Adjustment”
section) and de-energize the hot gas bypass solenoid
valves before proceeding.

4. On units with dual circuits, start only one circuit at a time.

To disable the second circuit compressors, refer to the
compressor sequencing information that shipped with the
compressor unit.

5. With the compressors operating, slowly open the “Low

Side” valve on the manifold gauge set. The remainder of
the refrigerant will be drawn into the system.

6. Once the charging for the operating circuit has been

completed, check and record the:

ambient temperature;
compressor oil level (each circuit);
compressor suction and discharge pressures (each
circuit);
superheat and subcooling (each circuit);

Record this data on an “operator’s maintenance log” like
the one shown in Table 5-5. If the operating pressures in-
dicate a refrigerant shortage, measure the system super-
heat and system subcooling. Repeat steps 1 through 6
for the second refrigeration circuit, if applicable.

Table 5-2

Minimum Starting Ambient Temperature

Standard

Low Ambient

Unit

With

No

With

No

Size

HGBP

HGBP

HGBP

HGBP

20 Ton

through

40

30

10

0

60 Ton

Note:
Minimum starting ambients in degrees F, based
on unit at minimum step of unloading and 5 mph
wind across the condenser.

Table 5-3

Recommended Refrigerant Capacities

Operating

Condenser

Unit

Charge per

Storage

Size

Circuit (1)

Capacity (2)

C20

25

67

C25

28

76

C30

37

96

C40

26

68

C50

28

71

C60

37

92

Notes:
1. CAUC-C20 - C30 are single-circuit units
    CAUC-40 - C60 are dual-circuit units
2. Pounds R-22 per circuit @ 95

o

F ambient,

    95% full.

Summary of Contents for CAUC-C20

Page 1: ...S Date October 2008 File No SV UN S S CAUC IOM 7 10 08 December 2001 s e d e s r e p u S TM Remote Air Cooled Condensers Models J and Later Design Sequence CAUC C20 CAUC C40 CAUC C25 CAUC C50 CAUC C3...

Page 2: ...ing the information within this manual and follow ing the instructions the risk of improper operation and or component damage will be minimized It is important that periodic maintenance be performed t...

Page 3: ...led Control Wiring 17 Refrigerant Piping 18 Liquid Lines 18 Liquid Line Components 18 Discharge Hot Gas Lines 18 Discharge Line Components 19 Making Refrigerant Connections 19 Brazing Procedures 19 Le...

Page 4: ...d just above the Mylar nameplate and a third nameplate is located on the inside of the control panel door When ordering replacement parts or requesting service be sure to refer to the specific model n...

Page 5: ...5 General Information Continued Unit Component Layout and Shipwith Locations 60 Ton Unit Illustrated...

Page 6: ...iate Trane office before installing or re pairing a damaged unit Unit Clearances Figure 3 1 illustrates the minimum operating and service clearances for either a single multiple or pit application The...

Page 7: ...7 Installation Continued Figure 3 1 Typical Installation Clearances for Single Multiple or Pit Applications...

Page 8: ...8 Figure 3 2 CAUC C20 Unit Dimensional Data Recommended Clearances...

Page 9: ...9 Figure 3 2 Continued CAUC C25 Unit Dimensional Data Recommended Clearances...

Page 10: ...10 Figure 3 2 Continued CAUC C30 Unit Dimensional Data Recommended Clearances...

Page 11: ...11 Figure 3 2 Continued CAUC C40 Unit Dimensional Data Recommended Clearances...

Page 12: ...12 Figure 3 2 Continued CAUC C50 Unit Dimensional Data Recommended Clearances...

Page 13: ...13 Figure 3 2 Continued CAUC C60 Unit Dimensional Data Recommended Clearances...

Page 14: ...g and Center of Gravity Data Location of Center of Shipping Gravity Unit Weight X Z Size Max Lbs In mm In mm C20 1348 41 1026 30 754 C25 1394 41 1031 30 762 C30 1585 41 1046 31 790 C40 2366 44 1115 43...

Page 15: ...y 2 Align the mounting holes in the base rail of the unit with the holes in the top of the appropriate isolator Refer to Figure 3 4 for the appropriate isolator for each load point 3 Install a 1 2 NC...

Page 16: ...the mounting surface Leveling the Unit Before tightening the mounting bolts level the unit carefully Use the unit base rail as a reference Level the unit to within 1 4 inch over its entire length Use...

Page 17: ...ssor unit Refer to the Refrigerant Piping section for recommended discharge line components and guide lines Install shutoff valves in the liquid line s to isolate the fil ter drier s for service Insta...

Page 18: ...e unit sheet metal for the refrigerant piping entrance into the unit Liquid Line Components Filter driers and valves expansion valves charging valves etc should be provided in the liquid lines just be...

Page 19: ...enter the system which will contaminate the re frigerant system 6 Apply heat evenly over the length and circumference of the joint to draw the brazing material into the joint by capillary action Remov...

Page 20: ...ection and re make as a new joint Retest for leaks after making re pairs 8 Open the liquid line service valve and the compressor discharge service valve Field Installed Power Wiring An overall dimensi...

Page 21: ...3 1 0 1 4 7 2 0 9 200 230 60 3 180 220 208 254 17 4 20 20 4 1 0 4 1 20 7 0 9 C40 460 60 3 416 508 7 7 15 15 4 1 0 1 8 9 0 0 9 575 60 3 520 635 6 15 15 4 1 0 1 4 7 2 0 9 200 230 60 3 180 220 208 254 25...

Page 22: ...RMER AND ANY OTHER LOAD RATED AT 1 AMP OR MORE Calculation 1 MCA MOP and RDE MCA 1 25 x LOAD 1 LOAD 2 LOAD 4 MOP 2 25 x LOAD 1 LOAD 2 LOAD 4 Select a fuse rating equal to the MOP value If the MOP valu...

Page 23: ...rol wir ing modifications must be made to the CAUC units Refer to Figure 3 7 and the field wiring diagram in the CCAD package chiller installation literature Follow the ap propriate procedure below fo...

Page 24: ...24 Figure 3 7 Typical Interface Connection Diagram for CCAD 20 through 60 Ton Package Chiller...

Page 25: ...25...

Page 26: ...tely 15 minutes This is referred to as a standing vacuum test where time versus pressure rise The maximum allowable rise over a 15 minute period is 200 microns If the pressure rise is greater than 200...

Page 27: ...vacuation Time vs Pressure Rise 200 400 600 800 1000 1200 1400 1600 10 0 10 20 30 40 50 60 70 80 90 TIME IN MINUTES PRESSURE IN MICRONS Continuously increasing pressure indicates the presence of leaks...

Page 28: ...rical Phasing Proper electrical phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Se quence Indicator and fo...

Page 29: ...dentification Customer Interlock 5K1 5K1 2B1 2B2 2B3 1 Circuit 1 Closed Open Customer Interlock 5K2 5K2 2B4 2B5 2B6 1 Circuit 2 Closed Open Fan 1S36 2 Temperature 67 5o F 65 F 2B3 1 Switch 1S37 2 67 5...

Page 30: ...power is applied 5 Check the condenser fans for proper rotation The direc tion of rotation is clockwise when viewed from the top of the unit All Fans are Rotating Backwards 1 Turn the field supplied d...

Page 31: ...cylinder to monitor the amount of refrigerant entering the system Refer to Table 5 3 for the recommended refrigerant capacities for the condensing unit The weight of refrigerant required for the liqui...

Page 32: ...r foot Table 5 5 Sample Operator s Maintenance Log Refrigerant Circuit 1 Refrigerant Circuit 2 Current Ambient Compr Suct Disch Liquid Super Sub Compr Suct Disch Liquid Super Sub Temp Oil Press Press...

Page 33: ...33 Blank...

Page 34: ...34 Figure 5 2 Typical Wiring Schematic for 20 through 60 Ton Units...

Page 35: ...35...

Page 36: ...36 Figure 5 3 Typical Control Panel Connections Diagram for 20 through 60 Ton Units...

Page 37: ...37...

Page 38: ...necessary Check the fan shaft bearings for wear Replace the bear ings as necessary Lubricate the supply fan bearings Refer to the equip ment manufacturer for their recommended greases Note Over lubri...

Page 39: ...brush and a sprayer either a garden pump up type or a high pressure sprayer A high quality detergent is also required suggested brands include SPREX A C OAKITE 161 OAKITE 166 and COILOX If the deterge...

Page 40: ...irement 26 L Leak testing a refrigerant system 20 Liquid Line Drier Refrigerant Requirements 32 See Figure 5 4 Liquid Line Filter Drier 18 Liquid Line Moisture Indicators 18 Liquid Line Solenoid Valve...

Page 41: ...tial start up warrantor will furnish a replace ment heat exchanger Warrantor s obligation and liabilities under this warranty are limited to furnishing replacement parts Warrantor shall not be obligat...

Page 42: ...42...

Page 43: ...43...

Page 44: ...44...

Reviews: