84
WSHP-PRC001-EN
Table P58: 006-060 Correction Factors for Variation in Entering Air Temperature
* = Sensible equals total capacity
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6
70.6
75.6
80.6
85.6
49.4
0.722
0.893
*
*
*
*
*
53.0
1.030
0.878
56.3
0.836
0.937
0.799
0.964
*
*
*
58.0
1.020
0.919
60.3
0.903
0.963
0.641
0.841
1.016
1.097
*
63.0
1.010
0.959
63.2
0.951
0.981
0.504
0.728
0.924
1.097
*
68.0
1.000
1.000
66.2
1.000
1.000
0.593
0.809
1.000
1.169
73.0
0.990
1.041
72.1
1.098
1.038
0.538
0.761
0.960
78.0
0.980
1.081
77.1
1.181
1.069
0.519
0.741
83.0
0.970
1.122
Performance Data
Correction Factors
Summary of Contents for Axiom GEH006
Page 107: ...WSHP PRC001 EN 107 Control Wiring Basic 24V 1 PH 208V 60HZ 1PH ...
Page 108: ...108 WSHP PRC001 EN Control Wiring Deluxe 24V 3 PH 208V 60HZ 3PH ...
Page 109: ...WSHP PRC001 EN 109 Control Wiring Tracer ZN510 1PH 208V 60HZ 1PH ...
Page 110: ...110 WSHP PRC001 EN Dimensional Data Tracer ZN524 3PH 460V 60HZ 3PH ...
Page 123: ...WSHP PRC001 EN 123 Dimensional Data Front Return Back Supply 12 1 2 15 Ton ...
Page 124: ...124 WSHP PRC001 EN Dimensional Data Back Return Front Supply 12 1 2 15 Ton ...
Page 125: ...WSHP PRC001 EN 125 Dimensional Data Front Return Top Supply 12 1 2 15 Ton ...
Page 126: ...126 WSHP PRC001 EN Dimensional Data Back Return Top Supply 12 1 2 15 Ton ...