Start-Up
WSHP-SVX01L-EN
87
GEVE042
042 (60 Hz)
036 (50 Hz)
68
7.8
122-140
242-308
12-15
20-26
122-140
318-404
9-12
31-41
042 (60 Hz)
036 (50 Hz)
68
9.8
121-140
234-298
9-12
20-26
126-144
321-409
7-9
31-42
042 (60 Hz)
036 (50 Hz)
75
7.8
123-141
267-340
12-15
20-25
136-156
331-422
10-13
33-44
042 (60 Hz)
036 (50 Hz)
75
9.8
122-141
259-330
9-12
20-26
140-161
336-427
8-10
34-45
042 (60 Hz)
036 (50 Hz)
86
7.8
126-144
307-390
11-15
19-25
160-184
355-452
11-14
38-49
042 (60 Hz)
036 (50 Hz)
86
9.8
125-144
299-380
9-12
19-25
166-190
359-457
9-12
39-50
042 (60 Hz)
036 (50 Hz)
95
7.8
127-147
345-439
11-14
18-24
—
—
—
—
042 (60 Hz)
036 (50 Hz)
95
9.8
127-146
337-428
9-11
18-24
—
—
—
—
GEHE048
048 (60 Hz)
042 (50 Hz)
35
—
—
—
—
—
74-85
263-334
6-8
20-29
048 (60 Hz)
042 (50 Hz)
35
—
—
—
—
—
76-87
265-337
5-6
20-29
048 (60 Hz)
042 (50 Hz)
45
9.0
120-138
184-234
13-16
23-29
85-98
273-348
7-9
23-32
048 (60 Hz)
042 (50 Hz)
45
11.2
120-138
176-225
10-13
23-29
87-100
275-350
6-7
23-33
048 (60 Hz)
042 (50 Hz)
55
9.0
121-140
214-273
13-16
23-28
101-117
289-368
8-10
26-36
048 (60 Hz)
042 (50 Hz)
55
11.2
121-139
206-262
10-13
23-28
104-120
292-372
6-8
26-36
048 (60 Hz)
042 (50 Hz)
68
9.0
125-144
256-326
13-16
22-28
117-135
305-388
9-12
30-40
048 (60 Hz)
042 (50 Hz)
68
11.2
125-144
247-315
10-13
23-28
122-140
310-394
7-10
30-41
048 (60 Hz)
042 (50 Hz)
75
9.0
126-146
282-359
12-16
22-28
131-151
318-405
10-13
32-43
048 (60 Hz)
042 (50 Hz)
75
11.2
126-145
273-348
10-13
22-28
136-156
322-410
8-10
33-44
048 (60 Hz)
042 (50 Hz)
86
9.0
129-148
324-412
12-15
21-27
154-177
339-431
11-14
36-47
048 (60 Hz)
042 (50 Hz)
86
11.2
128-147
314-400
10-12
22-27
160-184
344-437
9-12
37-48
048 (60 Hz)
042 (50 Hz)
95
9.0
130-150
364-463
12-15
21-27
—
—
—
—
048 (60 Hz)
042 (50 Hz)
95
11.2
130-149
354-451
10-12
21-27
—
—
—
—
Table 49. Operating pressures in cooling/heating for GE units (continued)
Operating Data
Model No.
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling
Heating
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop (°F)
Air Temp
Rise
(°F DB)
Summary of Contents for Axiom EXH018