Start-Up
100
WSHP-SVX01L-EN
Water Volume
Table 55, p. 100
is provided for use in calculating glycol
requirements for the unit.
Table 54. Heating water pressure drops (WPD) in feet of
head for EX units
Unit Size
(60 Hz)
Unit Size
(50 Hz)
EWT °F
GPM
Ft.
Pressure
EXH018
—
68
4.2
5.0
EXH024
—
68
5.6
7.9
EXH030
—
68
7
11.2
EXH036
—
68
8.4
6.5
EXH042
—
68
9.8
9.4
EXH048
—
68
11.2
9.4
EXH060
—
68
14
7.1
EXH070
—
68
15.4
7.2
EXV018
—
68
4.2
4.5
EXV024
—
68
5.6
8.2
EXV030
—
68
7
10.2
EXV036
—
68
8.4
7.5
EXV042
—
68
9.8
9.8
EXV048
—
68
11.2
9.1
EXV060
—
68
14
7.2
EXV070
—
68
15.4
7.6
Table 55. Water volume for GE units
Unit Size
(60 Hz)
Unit Size
(50 Hz)
Water Side
Volume
Cubic In.
Water Side
Volume
Cubic Ft.
Water Side
Volume
Gallons
006, 009
006
13.6
0.008
0.059
012, 015,
018
009, 015
28.2
0.016
0.122
024
018
37.8
0.022 0.164
030
024
49.1
0.028 0.213
GEV032,
GEV040
—
70.4
0.041 0.305
036
030
70.4
0.041 0.305
042
036
79
0.046 0.342
048
042
71.7 0.041 0.310
060
048
91.8
0.053 0.397
—
060
91.8
0.053 0.397
072
—
181.0
0.105
0.783
090
072
214
0.125
0.927
120
090
390
0.227
1.690
150, 180
120, 150
508
0.296
2.201
240
180
779
0.453
3.374
300
240
1057
0.615
4.576
Table 56. Water volume for EX units
Unit Size
(60 Hz)
Unit Size
(50 Hz)
Water Side
Volume
(in
3
)
Water Side
Volume
(ft
3
)
Water Side
Volume
(gallons)
EXH018
—
89.8
0.052
0.389
EXH024
—
89.8
0.052
0.389
EXH030
—
89.8
0.052
0.389
EXH036
—
171.2
0.099
0.741
EXH042
—
200.8
0.116
0.869
EXH048
—
200.8
0.116
0.869
EXH060
—
331.2
0.192
1.434
EXH070
—
331.2
0.192
1.434
EXV018
—
89.8
0.052
0.389
EXV024
—
89.8
0.052
0.389
EXV030
—
89.8
0.052
0.389
EXV036
—
171.2
0.099
0.741
EXV042
—
200.8
0.116
0.869
EXV048
—
200.8
0.116
0.869
EXV060
—
331.2
0.192
1.434
EXV070
—
331.2
0.192
1.434