Start-Up
WSHP-SVX01L-EN
81
GEHE/GEVE
012 (60Hz)
009 (50 Hz)
45
2.2
142-163
183-233
12-15
22-28
108-125
304-387
12-15
24-30
012 (60Hz)
009 (50 Hz)
45
2.8 142-163
175-223
9-12
23-29
111-128
307-391
9-12
24-31
012 (60Hz)
009 (50 Hz)
55
2.2
143-164
212-270
12-15
21-27
126-145
322-410
13-16
26-33
012 (60Hz)
009 (50 Hz)
55
2.8 143-164
204-260
9-12
22-27
130-149
325-413
10-13
27-34
012 (60Hz)
009 (50 Hz)
68
2.2
144-166
257-327
12-15
21-26
152-174
346-441
14-18
29-37
012 (60Hz)
009 (50 Hz)
68
2.8 144-166
248-316
9-12
21-26
157-180
352-448
11-15
29-37
012 (60Hz)
009 (50 Hz)
75
2.2
145-167
284-361
12-15
20-26
167-192
361-460
15-19
30-38
012 (60Hz)
009 (50 Hz)
75
2.8 145-167
274-349
9-12
20-26
173-199
366-466
12-15
30-39
012 (60Hz)
009 (50 Hz)
86
2.2
146-168
332-422
12-15
19-25
194-223
384-489
16-21
32-40
012 (60Hz)
009 (50 Hz)
86
2.8 146-168
321-409
9-12
20-25
201-231
390-497
13-17
32-41
012 (60Hz)
009 (50 Hz)
95
2.2
147-170
376-478
12-15
19-24
—
—
—
—
012 (60Hz)
009 (50 Hz)
95
2.8 147-170
365-465
9-12
19-24
—
—
—
—
015 (60Hz)
012 (50 Hz)
35
2.8
—
—
—
—
91-105
296-377
6-7
20-25
015 (60Hz)
012 (50 Hz)
35
3.5 —
—
—
—
93-107
299-380
5-6
20-26
015 (60Hz)
012 (50 Hz)
45
2.8
138-159
180-230
11-14
22-28
107-123
313-398
7-8
23-29
015 (60Hz)
012 (50 Hz)
45
3.5 138-158
174-221
9-11
22-27
109-126
316-402
5-7
23-30
015 (60Hz)
012 (50 Hz)
55
2.8
139-159
210-267
11-14
21-27
124-143
332-423
8-10
26-33
015 (60Hz)
012 (50 Hz)
55
3.5 138-159
203-258
9-11
21-27
128-147
336-427
6-8
27-34
015 (60Hz)
012 (50 Hz)
68
2.8
140-161
254-324
11-14
20-26
150-172
358-456
9-11
30-38
015 (60Hz)
012 (50 Hz)
68
3.5 140-161
246-313
9-11
21-26
154-178
364-463
7-9
30-39
015 (60Hz)
012 (50 Hz)
75
2.8
141-162
281-358
11-14
20-25
165-190
373-475
10-12
32-40
015 (60Hz)
012 (50 Hz)
75
3.5 140-162
272-347
9-11
20-26
171-196
379-483
8-10
32-41
015 (60Hz)
012 (50 Hz)
86
2.8
142-163
328-417
11-14
19-25
191-220
399-508
11-14
34-43
015 (60Hz)
012 (50 Hz)
86
3.5 142-163
318-405
9-11
20-25
198-228
405-515
9-11
34-44
Table 49. Operating pressures in cooling/heating for GE units (continued)
Operating Data
Model No.
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling
Heating
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop (°F)
Air Temp
Rise
(°F DB)
Summary of Contents for Axiom EXH018