
32
HDWA-SVX001D-EN
Pressure Testing Waterside
Piping
N
NO
OT
TIIC
CE
E
E
Eq
qu
uiip
pm
me
en
ntt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w tth
he
esse
e iin
nssttrru
uccttiio
on
nss cco
ou
ulld
d rre
essu
ulltt iin
n
e
eq
qu
uiip
pm
me
en
ntt d
da
am
ma
ag
ge
e..
D
Do
o n
no
ott o
ov
ve
err p
prre
essssu
urriizze
e tth
he
e ssy
ysstte
em
m o
orr e
ex
xcce
ee
ed
d
d
de
essiig
gn
n p
prre
essssu
urre
e.. A
Allw
wa
ay
yss p
pe
errffo
orrm
m a
a h
hy
yd
drro
o p
prre
essssu
urre
e
tte
esstt w
wiitth
h w
wa
atte
err p
prre
esse
en
ntt iin
n p
piip
piin
ng
g a
an
nd
d w
wa
atte
errb
bo
ox
xe
ess..
Waterside design pressure is 150 psig (1034.2 kPaG).
Eddy Current Testing
Trane recommends conducting an eddy current
inspection of the condenser and evaporator tubes in
water-cooled chillers every three years. Eddy current
tests are intended to identify defects on or within the
walls of heat exchanger tubing that could lead to in-
service tube failures. Eddy current tests conducted
before a chiller is put into service are considered
“baseline” eddy current tests, and are intended to
establish a reference point to aid in the interpretation of
future eddy current test reports. Many of the anomalies
that can be found through eddy current testing have no
impact on tube life or performance, while others are
severe enough to justify removing the affected tube
from service. Ask your sales account manager for a
copy of the engineering bulletin (CTV-PRB024*-EN) for
clarification of the role of eddy current testing in chiller
maintenance by providing information about eddy
current technology and heat exchanger tubing.