24
HDWA-SVX001D-EN
Table 8. Agility chiller control settings based on propylene glycol percentage (continued)
Propylene
Glycol
Percentage, %
Solution Freeze Point
Minimum Recommended LRTC
Minimum Recommended LWTC
°F
°C
°F
°C
°F
°C
22
17.6
-8.0
14.2
-9.9
19.6
-6.9
24
15.7
-9.0
12.3
-10.9
17.7
-7.9
25
14.8
-9.6
11.4
-11.5
16.8
-8.5
26
13.8
-10.1
10.4
-12.0
15.8
-9.0
28
11.6
-11.3
8.2
-13.2
13.6
-10.2
30
9.3
-12.6
5.9
-14.5
11.3
-11.5
32
6.8
-14.0
3.4
-15.9
8.8
-12.9
34
4.1
-15.5
0.7
-17.4
6.1
-14.4
35
2.7
-16.3
-0.7
-18.1
5.0
-15.0
36
1.3
-17.1
-2.1
-19.0
5.0
-15.0
38
-1.8
-18.8
-5.2
-20.7
5.0
-15.0
40
-5.2
-20.7
-8.6
-22.5
5.0
-15.0