Installation
Reprogramming factory installed AdaptiView controls (CTV firmware)
Important:
Make sure your laptop is loaded with the most current version of Tracer TU tool
software so that you have the most up-to-date version of CTV MP firmware available
to install into the UC800.
Note:
CTV MP firmware is always used in factory installed AdaptiView control systems or in
AdaptiView display upgrades to factory installed CH530 control systems.
Table 23. UC800/AdaptiView CTV parameter values with a retrofit AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
Range
Default Setting
Recommended Setting
AF Control
Auto, Fixed
Auto
Auto
ReOptimization Sensitivity
0 - 100%
20
20
Tracer TU Field Startup View:
Adjustable Frequency Drive
Range
Default Setting
Recommended Setting
Maximum Frequency
38 - 60 Hertz
60
60
Minimum Frequency
38 - 60 Hertz
38
38
AFD Surge Capacity Increase
0 - 5%
1
1
Tracer TU Configuration View: Main
Range
Default Setting
Recommended Setting
Unit Type (MODL)
CVHE, CVHF, CVHG, CVGF
CVHE
Enter Chiller Model from Unit Nameplate
(Note: only CVHE or CVHF apply)
Tracer TU Configuration View: UC800
Range
Default Setting
Recommended Setting
Starter Type
Not Applicable
Unit Mount Wye-Delta
Remote Mount Non-Comm AFD
Impeller Diameter (CPIM)
210 - 335
275
Enter CPIM from Unit Nameplate
Tracer TU Configuration View: Starter
Range
Default Setting
Recommended Setting
Stop Delay Time (Contactor Interrupt Failure)
1 - 30 Seconds
3
30
Unit Voltage
180 - 15000 Volts
460
Enter from Unit Nameplate
Voltage Transformer Ratio
0 - 700
20
Enter from Unit Nameplate
Rated Load Amps (RLA)
0 - 2500 Amps
500
Enter from Unit Nameplate
CT Meter Scale
0 - 2000
0
Choose Correct CT Meter Scale from
Current Unbalance Trip Point
15 - 100%
30
30
Current Unbalance Grace Period
10 - 255 Seconds
90
90
Maximum Acceleration Setting
6 - 64 Seconds
6
6
Acceleration Time Out Action
Shutdown, Transition
Shutdown
Shutdown
Overload Type
Exponential, Linear
Linear
Linear
Phase Reversal
Enable, Disable
Enable
Disable
Contactor Integrity Test
Enable, Disable
Disable
Disable
Phase Reversal Grace Period
20 - 1000 milliseconds
700
1000
Surge Protection
Enable, Disable
Enable
Enable
Momentary Power Loss Protection
Enable, Disable
Enable
Disable
Restart Inhibit Stop to Start Time
0 - 255 Seconds
30
60
Surge Sensitivity
0 - 100%
20
20
Power Loss Reset Time
0 - 255 Seconds
15
15
RTD Type
75 Ohm@75F, 100 Ohm@ 0C
75 ohm
75 ohm
Summary of Contents for AFDH
Page 11: ...AFDH SVN01A EN 11 Nameplates Note This page has been intentionally left blank...
Page 65: ...AFDH SVN01A EN 65 Installation Note This page intentionally left blank...
Page 66: ...66 AFDH SVN01A EN Installation Note This page intentionally left blank...
Page 67: ...AFDH SVN01A EN 67 Installation Note This page intentionally left blank...