AFDH-SVN01A-EN
57
Installation
AFDH drive program parameters used with all Trane controls
Important:
Any AFDH drive module menu parameter numbers not listed in this manual are non-
Trane specific program parameters. All non-Trane specific program parameter
values have been set by the manufacturer before shipment, to provide optimum
drive performance. Under no circumstances should any of the pre-set values in
these menu parameters be changed unless specifically directed to do so by a factory
engineer or a factory technical support person.
Note:
Please refer to the TR1-SVX10A-EN TR1™ Series Variable Frequency Drive Installation and
Operation manual for full program parameter details and descriptions, and the instructions
necessary to operate the Local Control Panel (LCP) and program the necessary drive
parameters.
•
Please refer to the table below for the Trane specific menu parameters that must be reviewed
and/or programmed into the AFDH drive module before doing the initial machine start-up.
Table 18. Trane specific AFDH program parameters and settings
Parameter
Number
(a)
Parameter Name
Default Value
(Value Description)
Recommended Value to Use
(Value Description)
007
Large Readout
4 (Frequency %)
3 (Frequency Hz)
008
Small Readout 1
1 (Reference %)
5 (Motor Current)
009
Small Readout 2
5 (Motor Current A)
6 (Power KW)
010
Small Readout 3
7 (Power HP)
27 (Heat Sink Temp)
012
Hand Start on LCP (Hand start button)
1 (Enable)
0 (Disable)
013
Off/Stop on LCP (Stop button)
1 (Enable)
0 (Disable)
101
Torque Characteristics
0 (Automatic Energy Optimization)
1 (Multiple Motors)
102
Motor Power
None - Read Motor Nameplate
Enter Nameplate Motor CPKW
103
Motor Voltage
None - Read Motor Nameplate
Enter Motor Voltage from Nameplate
104
Motor Frequency
None - Read Motor Nameplate
60 (Hz)
105
Motor Current
None - Read Motor Nameplate
Enter RLA from Motor Nameplate
106
Rated Motor Speed
None - Read Motor Nameplate
Enter RPM from Motor Nameplate
201
Output Frequency Low Limit
0.0 (Hz)
38 (Hz)
202
Output Frequency High Limit
60 (Hz)
60 (Hz)
204
Minimum Reference
0.0 (Hz)
Enter 38 (Hz)
205
Maximum Reference
60 (Hz)
60 (Hz)
206
Ramp-Up Time
None
10 (Seconds)
207
Ramp-Down Time
None
20 (Seconds)
215
Current Limit
None - Read Drive Nameplate
Enter Maximum Rated Drive Amps
304
Coast Inverse
3 (Safety Interlock)
0 (Coasting Stop, Inverse)
308
Terminal 53 Analog Input Voltage
0 (No Operation)
1 (Reference)
309
Terminal 53 Minimum Scaling
0.0 (Volts)
2 (Volts)
314
Terminal 60 Analog Input Current
0 (No Operation)
0 (No Operation)
323
Relay 1 Function
0 (No Alarm)
8 (Alarm)
(a) Note: Highlighted parameter rows indicate values that must be programmed in the field. Non-highlighted parameter rows should have been factory
set to the recommended value to use - review these parameters and change to recommended value if necessary.
Summary of Contents for AFDH
Page 11: ...AFDH SVN01A EN 11 Nameplates Note This page has been intentionally left blank...
Page 65: ...AFDH SVN01A EN 65 Installation Note This page intentionally left blank...
Page 66: ...66 AFDH SVN01A EN Installation Note This page intentionally left blank...
Page 67: ...AFDH SVN01A EN 67 Installation Note This page intentionally left blank...