 18-AD35D1-2D-EN

Installer’s Guide

Is sub cooling at the

outdoor unit between

8 to 12F?

Troubleshooting Indoor TXV / Cooling Mode

NO

YES

Is superheat

< 5F?

YES

Correct air

flow

problem

Is air flow at least

350 CFM per ton?

YES

NO

Remove sensing bulb from the

suction line. Measure superheat

at indoor coil while holding the

bulb in bare hand for one minute.

Does superheat decrease?

Measure superheat at indoor coil

while placing the bulb in an ice

and water bath for one minute.

Does superheat increase?

YES

Replace the

TXV

TXV is OK

NO

Is superheat

< 25F?

YES

NO

Is indoor

temperature more

than 85F?

NO

Is sub cooling less

than 8F?

YES

Confirm that charge

is correct and look

for dirty or restricted

outdoor coil.

Confirm that

charge is

correct.

NO

Before starting

, insure the

blower wheel, indoor and outdoor

coils are clean.

Is the liquid line

temperature at indoor

coil within 8F of outdoor

liquid line temperature?

YES

Verify line set is

sized properly

for application

NO

The system is running at max

capacity and this may be

causing the High superheat.

Wait until indoor temperature

is less than 80F and check

superheat again.

YES

YES

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Summary of Contents for 4TXCA002DS3HCA

Page 1: ...oil before beginning the installation Figure 1 18 AD35D1 2D EN Cased Aluminum Convertible Coils Models 4TXCA002DS3HCA 4TXCA032DS3HCA 4TXCB003DS3HCA 4TXCB004DS3HCA 4TXCB006DS3HCA 4TXCC005DS3HCA 4TXCC00...

Page 2: ...ency a Remove the coil by sliding the coil out of the coil enclo sure b Optional but recommended Remove the factory in stalled two piece baffle assembly from the top of the coil by removing the 5 16 h...

Page 3: ...mmended On 4TXCC009DS and 4TXCD010DS only remove the 2 outer water diverter baffles by removing the 5 16 hex head screws See Fig ure 6 IMPORTANT The 4TXC cased coil must be placed downstream of the fu...

Page 4: ...condensing downflow hori zontal and upflow horizontal furnaces may only be rotated onto their left side Connection brackets for coil furnace alignment are included with the furnaces a In horizontal le...

Page 5: ...rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run th...

Page 6: ...for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insula...

Page 7: ...ALL WIDTH B IN 14 1 2 14 1 2 17 1 2 21 17 1 2 21 21 OPENING WIDTH C IN 13 5 8 13 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3...

Page 8: ...T LBS 50 REFRIGERANT CONTROL TXV NON BLEED HEIGHT A IN 17 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION 3 4 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO...

Page 9: ...EED HEIGHT A IN 26 7 8 30 11 16 OVERALL WIDTH B IN 24 1 2 24 1 2 OPENING WIDTH C IN 23 5 8 23 5 8 TOP OPENING D 22 3 4 22 3 4 GAS CONNECTION 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Page 10: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is c...

Page 11: ...18 AD35D1 2D EN 11 Installer s Guide...

Page 12: ...icy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact you...

Reviews: