background image

18-BC96D1-1A-EN 

 

    21 

STEP 9 

- Record System Information for refer-

ence. 

Record system pressures and temperatures 
after charging is complete.

Outdoor model number = _________________

Measured Outdoor Ambient = __________  º F

Measured Indoor Ambient = __________  º F

Measured Liquid Line Temp = __________  º F

The Subcooling Charging method in cooling is 

not

 recommended below 55º F outdoor temperature.

The only recommended method of charging at outdoor temperatures below 55º F is weighing in the charge in 

heating mode

 and referencing the refrigerant pressure curves for typical performance.

STEP 1

 - Determine additional charge.

Note

:

 The nameplate charge value represents 

the amount of refrigerant shipped in the outdoor 
unit and is compatible with 15 feet of AHRI rated 
refrigerant lines and the smallest AHRI rated 
coil.

Using the method below, find the charge associ-
ated with the additional length of tubing above 
15 ft. and record it below.

14.3 Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)

Measured Suction Line Temp = __________  º F

Liquid Gage Pressure = __________ PSIG

Suction Gage Pressure = __________ PSIG

Calculating Charge Using the Weigh-In Method

1)  

Measure in feet the distance between the 

outdoor unit and the indoor unit. (Include 
the entire length of the line from the service 
valve to the IDU.) Subtract 15 ft from this 
entire length and record on line 1.

2)  

Enter the charge multiplier (0.6 oz/ft).  Each 

linear foot of interconnecting tubing requires 
the addition of 0.6 oz of refrigerant.

3)  

Multiply the total length of refrigerant tubing 

(Line 1) times the value on Step 2. Record 
the result on Line 3 of the Worksheet.

4)  

This is the amount of refrigerant to weigh-in 

prior to opening the service valves.

1.  Total Line length (ft) –15 ft   ______________

2.  Charge multiplier 

x  ___0.6 oz _____

3.  Step 1 x Step 2 

=  _____________

4.  Refrigerant (oz) 

 _____________

Weigh-In Method can be used for the initial 
installation, or anytime a system charge is being 
replaced. Weigh-In Method can also be used 
when power is not available to the equipment 
site or operating conditions (indoor/outdoor 
temperatures) are not in range to verify with the 
subcooling charging method.

Summary of Contents for 4TWA7

Page 1: ...pproved matched indoor and outdoor systems All of the manufacture s split systems are AHRI rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and out doo...

Page 2: ...ponent replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening...

Page 3: ...sions and Weight Models H x D x W in Weight lb 4TWA7036A3 4 45 x 34 x 37 245 4TWA7048A3 4 45 x 34 x 37 265 4TWA7060A3 4 45 x 34 x 37 265 Weight values are estimated 1 The maximum TOTAL length of refri...

Page 4: ...areas where snow accumulation and prolonged below freezing temperatures occur Units should be elevated 3 12 inches above the pad or roof top depending on local weather This additional height will all...

Page 5: ...pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad must be separate from any structure The pad must be level The pad should be h...

Page 6: ...4 7 8 3 8 7 8 3 8 150 50 4TWA7060A3 4 1 1 8 3 8 7 8 3 8 80 25 ALTERNATE LINE SIZES Line Sizes Service Valve Connection Sizes Max Line Lift Lengths Vapor Line Liquid Line Vapor Line Connection Liquid L...

Page 7: ...line length and lift You will need this later in STEP 2 of Section 14 Total Line Length __________ Ft Total Vertical Change lift __________ Ft Trane outdoor condensing units are factory charged with...

Page 8: ...rom the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolation hangers should also be used wh...

Page 9: ...e or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant L...

Page 10: ...ier check liquid line filter drier s directional flow arrow to confirm correct direction of refrigeration flow away from outdoor unit and toward evapo rator coil as illustrated Braze the filter drier...

Page 11: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Le...

Page 12: ...ete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUN...

Page 13: ...ve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches...

Page 14: ...to the service information in control box Defrost Board Detail Jumper J2 J5 Test Pins 11 3 Defrost Control With TEM 6 Thermostat Air Handler Outdoor Unit R G B W1 W2 R B O X2 R G B C B C O Y1 W Blue...

Page 15: ...gh Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be...

Page 16: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is...

Page 17: ...ent tempera ture is above 55 F For best results the indoor temperature should be kept between 70 F to 80 F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 3 Total Lin...

Page 18: ...NG CHART CORRECTIONS TABLE FOR LINE LENGTH AND RISE Add 2 REFRIGERANT LINE LIFT FT 4 Ton Heat Pump 50 1 40 1 30 25 Use Design Subcooling 15 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 REFRIGE...

Page 19: ...essure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 1...

Page 20: ...OR TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER IND...

Page 21: ...eating Only Measured Suction Line Temp __________ F Liquid Gage Pressure __________ PSIG Suction Gage Pressure __________ PSIG Calculating Charge Using the Weigh In Method 1 Measure in feet the distan...

Page 22: ...btained with the namplate charge plus additional charge previously added STEP 5 Return to site for adjustment Important Return in the spring or summer to accurately charge the system in the cooling mo...

Page 23: ...gainst the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Importa...

Page 24: ...A R G E E X C E S S I V E E V A P L O A D N O N C O N D E N S A B L E S R E S O D A I R F L O W O D A I R R E C I R C U L A T I O N T X V E E V S T U C K O P E N S U P E R H E A T R E S I D A I R F L...

Reviews: