 A.  GENERAL

These coils are designed for use as cooling only or in 

combination with a Heat Pump outdoor section.

B.  APPLICATION INFORMATION

1.  FURNACE AND COIL  

 

Coil MUST BE installed downstream (discharge air)  

of the furnace.

2.  INDOOR UNIT AIRFLOW 

Indoor unit must provide the required airflow for 

Cooling only or Heat Pump System Combination.

INSPECTION

Check carefully for any shipping damage. This must be 

 reported to and claims made against the transportation 

com pany immediately. Check to be sure all major 

components are in the unit. Any missing parts should 

be reported to your supplier at once, and replaced with 

authorized parts only.

Horizontal, Flat “Cased” Coils

Copper/Aluminum Coils: 4PXFH001BC3HHA, 4PXFH003BZ3HHA, 

4PXFH004BC3HHA, 4PXFH005BZ3HHA, 4PXFH007BC3HHA, 

4PXFH009BZ3HHA

Installer’s Guide

 C.  RECOMMENDATIONS

CAUTION

!

This coil is pressurized with 8-12 psig of dry air. Do 
not stand directly in front of the coil connections 
when removing sealing plugs. If no pressure is 
released, check for leaks.

1.  If this coil is a part of the total system installation, then 

use the Installer’s Guide packaged with the furnaces, 

Heat Pump outdoor sections, and Control Center for 

physically installing those components.

2.  It is recommended that the outline drawing  

(page 2) be studied and dimensions properly noted 

and checked against selected installation site. By 

noting in advance proper clearance allowances for 

installation and possible future service of the coil.

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — 

This Document is 

customer property and is to remain with 

this unit. Please return to service information pack 

upon completion of work.

18-AD40D1-1B-EN

WARNING

!

This product can expose you to chemicals including lead, 

which are known to the State of California to case cancer and 

birth defects or other reproductive harm. For more information 

go to www. P65Warnings.ca.gov

D.  INSTALLING 4PXFH COIL/ 

ENCLOSURE

Coil/enclosure assembly can be used for all horizontal 

furnaces (gas and electric) applications (Figure 1), and 

for applications of vertical upflow furnaces (Figure 2), 

where the top clearance is insufficient for installing an 

“A” coil and enclosure, and there is access to a run of 

horizontal duct.

SUPPLY DUCT

2 FEET MINIMUM

RECOMMENDED

FURNACE

FLUE STACK

TRANSITION DUCT

COIL/ENCLOSURE ASSY

WARNING

!

WARNING (Medium/high pressure) 

Contains Refrigerant!

System contains oil and refrigerant under high pressure.  

Recover refrigerant to relieve  pressure before opening 

the system. See unit nameplate for refrigerant type. Do not 

use non-approved refrigerants, refrigerant substitutes, or 

refrigerant additives. 
Failure to follow proper procedures or the use of non-

approved refrigerants, substitutes, or refrigerant additives 

could result in death, serious injury, or equipment damage.

Summary of Contents for 4PXFH001BC3HHA

Page 1: ...checked against selected installation site By noting in advance proper clearance allowances for installation and possible future service of the coil ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work 18 AD40D1 1B EN WARNING This...

Page 2: ... B A 5 00 6 50 0 75 FLANGES TYP 6 81 1 75 SUCTION TUBE SEE TABLE FOR SIZES 3 8 LIQUID LINE D OPENING C E 3 00 MAX TRANE MODEL A B C D E SUCTION SIZE 4PXFH003BZ3HHA 10 23 50 21 30 35 50 3 4 4PXFH001BC3HHA 10 23 50 21 24 29 50 3 4 4PXFH005BZ3HHA 10 23 50 21 30 35 50 3 4 4PXFH004BC3HHA 10 23 50 21 30 35 50 7 8 4PXFH007BC3HHA 10 23 50 21 30 35 50 7 8 4PXFH009BZ3HHA 10 29 50 27 34 41 50 7 8 ISOMETRIC V...

Page 3: ...e coil or drainpan Areas to be avoided include the back bottom front top center and lower 3 of the left and right sides of the coil cabinet 6 The indoor coil must be evacuated through the refrigerant lines at the outdoor unit before opening the service valves See evacuation procedure in Field Fabricated Refrigerant Lines section of the Installer s Guide for the outdoor unit 7 Complete the installa...

Page 4: ... assembly The female threaded fitting protrudes outside of the enclosure for external connection A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insulation 2 Insulate the primary drain line to prevent sweating where...

Page 5: ...oth section of suction vapor line using the metal clamp provided In order to obtain a good temperature reading and correct superheat control the TXV sensing bulb must conform to the following criteria 1 The sensing bulb must be in direct and continuous contact with the suction line 2 The sensing bulb should be mounted horizontally on the suction line 3 The sensing bulb should be mounted at the 2 o...

Page 6: ...perature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is sized properly for application NO The syst...

Page 7: ...18 AD40D1 1B EN 7 Installer s Guide Wrap TXV with wet cloth before brazing Direct torch away from wrapped valve ...

Page 8: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2022 18 AD40D1 1B EN 24 Jan 2022 Supersedes 18 AD40D1 1A EN December 2020 ...

Reviews: