background image

 18-AD40D1-1B-EN

Installer’s Guide

3.  Swedge using approved industry practices, or use 

field supplied coupler, on indoor unit coil connections.  

Connect field supplied refrigerant tubing to coil 

connections.

4.  Flow a small amount of nitrogen through the tubing    

while brazing.

5.  Use good brazing technique to make leakproof joints.

6.  Minimize the use of sharp 90 degree bends.

7. 

Insulate the suction line and its fittings.

8.  Do NOT allow un-insulated lines to come into contact 

with each other.

F.  LEAK CHECK

1.  Using a manifold gauge, connect an external supply  

of dry nitrogen to the gauge port on the liquid line.  

2.  Pressurize the connecting lines and indoor coil to 

150 PSIG maximum.

3.  Leak check brazed line connections using soap 

bubbles. Repair leaks (if any) after relieving pressure.

4.  Evacuate and charge the system per the instructions 

packaged with the outdoor unit.

G.  CONDENSATE DRAIN PIPING 

    (SEE FIGURE 3)

NOTE:

When coils are installed above ceilings or in other 

locations where damage from condensate overflow 

may occur, a field fabricated auxiliary drain pan 

shall be installed under the coil enclosure. Drain 

lines from this pan must be installed, but should 

NOT be connected to the primary pan. These drain 

lines should terminate in an area easily seen by the 

homeowner, but not located to drip on sidewalks or 

other slip hazard areas. 

Condensate drain connections are located in the drain 

pan at the bottom of the coil/enclosure assembly. The 

female threaded fitting protrudes outside of the enclosure 

for external connection. A field fabricated trap is not 

required for proper drainage due to the positive pressure 

of the furnace; however, it is recommended to prevent 

efficiency loss of conditioned air. 

1.  The drain hole in the drain pan must be cleared of all 

insulation.

2.  Insulate the primary drain line to prevent sweating 

where dew point temperatures may be met. (Optional 

depending on climate and application needs).

3.  Connect the secondary drain to a separate drain 

line (no trap is needed in this line). The secondary 

drain should terminate in an area easily seen by the 

homeowner, but not located to drip on sidewalks or 

other slip hazard areas.

4.  Test drainage of all condensate lines prior to 

completing installation.

IMPORTANT:

Plug all drain line connection(s) not used. Do NOT 

use heat or torch near drain fittings.

H.  DUCT CONNECTIONS

The supply and return air duct should be connected to 

the unit with a flame retardant duct connectors. Duct 

flange connections are provided at both supply and 

discharge openings of the coil.

FIELD FABRICATED TRAP

2" MIN.

2" MIN.

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 

of furnace / air handler

condensate drain connection.

Close as possible

There is only a holding charge of dry air in the indoor coil, 

therefore no loss of operating refrigerant charge occurs 

when the sealing plugs are removed.
1.  Remove sealing plugs and use pipe cutter to remove 

spun closed ends.

2.  Field supplied tubing should be cut square, round 

and free of burrs at the connecting end. Clean the 

tubing to prevent contaminants from entering the 

system.

Summary of Contents for 4PXFH001BC3HHA

Page 1: ...checked against selected installation site By noting in advance proper clearance allowances for installation and possible future service of the coil ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work 18 AD40D1 1B EN WARNING This...

Page 2: ... B A 5 00 6 50 0 75 FLANGES TYP 6 81 1 75 SUCTION TUBE SEE TABLE FOR SIZES 3 8 LIQUID LINE D OPENING C E 3 00 MAX TRANE MODEL A B C D E SUCTION SIZE 4PXFH003BZ3HHA 10 23 50 21 30 35 50 3 4 4PXFH001BC3HHA 10 23 50 21 24 29 50 3 4 4PXFH005BZ3HHA 10 23 50 21 30 35 50 3 4 4PXFH004BC3HHA 10 23 50 21 30 35 50 7 8 4PXFH007BC3HHA 10 23 50 21 30 35 50 7 8 4PXFH009BZ3HHA 10 29 50 27 34 41 50 7 8 ISOMETRIC V...

Page 3: ...e coil or drainpan Areas to be avoided include the back bottom front top center and lower 3 of the left and right sides of the coil cabinet 6 The indoor coil must be evacuated through the refrigerant lines at the outdoor unit before opening the service valves See evacuation procedure in Field Fabricated Refrigerant Lines section of the Installer s Guide for the outdoor unit 7 Complete the installa...

Page 4: ... assembly The female threaded fitting protrudes outside of the enclosure for external connection A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insulation 2 Insulate the primary drain line to prevent sweating where...

Page 5: ...oth section of suction vapor line using the metal clamp provided In order to obtain a good temperature reading and correct superheat control the TXV sensing bulb must conform to the following criteria 1 The sensing bulb must be in direct and continuous contact with the suction line 2 The sensing bulb should be mounted horizontally on the suction line 3 The sensing bulb should be mounted at the 2 o...

Page 6: ...perature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is sized properly for application NO The syst...

Page 7: ...18 AD40D1 1B EN 7 Installer s Guide Wrap TXV with wet cloth before brazing Direct torch away from wrapped valve ...

Page 8: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2022 18 AD40D1 1B EN 24 Jan 2022 Supersedes 18 AD40D1 1A EN December 2020 ...

Reviews: