background image

© 2010 Trane

18-AC51D5-5

Installer’s Guide

C. ACCUTRON™ FLOW CONTROL VALVE

If the indoor unit System Refrigerant Flow control is an
Accutron™ orifice and check valve assembly, an orifice size
change may be necessary.  See Figure 3.

The outdoor model determines the required orifice size. Check
the listed orifice size on nameplate of the selected outdoor
model. If the indoor unit is factory shipped with a different
orifice size, the orifice must be changed to obtain system
rated performance.

IMPORTANT:

The outdoor unit is shipped with the proper size orifice and a
stick-on orifice size label in an envelope attached to the outdoor
unit. Outdoor unit nameplate will have correct orifice size
specified as BAYFCCV---A for rated performance.

D. INSTALLING REFRIGERANT LINES

CAUTION

!

If using existing refrigerant lines make certain that all joints
are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon situa-
tion requirements.  This should be thoroughly checked out
before ordering refrigerant line sets.

The gas line must always be insulated.

CAUTION

!

In scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor
to severe burning.

IMPORTANT:

The unit has a NITROGEN holding charge which will need to
be evacuated before charging per local system application
requirement.

Refrigerant charge adjustment is necessary. 

Use the

Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space

limitations.

NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.

3. Determine the best starting point for routing the refriger-

ant tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both

liquid and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly

secure the tubing before making connections.

8. To prevent a noise within the building structure due to

vibration transmission from the refrigerant lines, the
following precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation
type hangers.

b. Isolation hangers should also be used when refriger-

ant lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill,

they should be insulated and isolated.

d. Isolate the lines from all ductwork.

E. SERVICE VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES

The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory charge.  The
pressure tap service port (when depressed) opens only to the
field brazing side of the valve when the valve is in the seated
position.  The liquid line valve is 

not 

a back seating valve

(see

 WARNING 

below).

WARNING

!

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclock-
wise only until the stem contacts the rolled edge. (See
Figure 4) No torque is required.

BRASS GAS LINE BALL SERVICE VALVE

The Brass Gas Line Ball Service Valve is shipped in the
closed position to hold the factory refrigerant charge.  The
pressure tap service port (when depressed) opens only to the
field brazing  side when the valve is in the closed position. The
Gas Line Ball Service Valve is full open with a 1/4 turn.  See
Figure 5.

BRAZING REFRIGERANT LINES

1. Remove lower access cover to access service valves.

2. Before brazing, remove plugs from external copper stub

tubes.  Clean internal and external surfaces of stub
tubes prior to brazing.

BASEPAN TAB REMOVAL

2

SEALING CAP

ADAPTER

FLOW CONTROL
CHECK VALVE
(F.C.C.V.) ORIFICE

FIELD SUPPLIED
LIQUID LINE

AS SHIPPED

BODY

ACCUTRON

TM

COMPONENTS

BRAZE TYPE INDOOR END

3

Summary of Contents for 2TTA0030

Page 1: ...an Remove tabs by cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is no...

Page 2: ...E OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route...

Page 3: ...erant charge the gas and liquid line valves must remain closed 1 Upon completion of leak check evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves 2 Attach app...

Page 4: ...lectrical conduit whenever vibration transmission may create a noise problem within the structure G COMPRESSOR START UP After all electrical wiring is complete SET THE THERMO STAT SYSTEM SWITCH IN THE...

Page 5: ...grounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to...

Page 6: ...28 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0040AD 2 2 730 28 3 4 724 28 1 2 651 25 5 8 1 1 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0050AD 3 1...

Page 7: ...18 AC51D5 5 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0...

Page 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Reviews: