BAS-SVP046A-EN
15
Table 6. ACRB 350–500 tons network variable outputs (continued)
nv
Index
Configuration
Variable Name
Variable Type
Variable description
Delta to Send
(Notes)
SendHrdBt
Point Name
53
nvoOutdoorTemp
SNVT_temp_p
Outdoor Air Temperature
1.00°C
♥
Outdoor Air Temperature
58
nvoEvapAprchTmp
SNVT_temp_diff_p
Evaporator Approach
Temperature
0.50°C
♥
Evaporator Approach
Temperature
62
nvoUnitVoltage
UNVT_3phase_volt
Unit Voltage Per Phase
defined at element
♥
SNVT_volt_ac
BC voltage
Note 1
Starter Voltage Phase BC
SNVT_volt_ac
CA voltage
Note 1
Starter Voltage Phase CA
SNVT_volt_ac
AB voltage
Note 1
Starter Voltage Phase AB
64
nvoEvapRfgtPrsC1
SNVT_press_f
Evaporator Refrigerant
Pressure - Circuit 1
5.0 kPa
♥
Evaporator Refrigerant
Pressure Ckt1
65
nvoEvapRfgtPrsC2
SNVT_press_f
Evaporator Refrigerant
Pressure - Circuit 2
5.0 kPa
♥
Evaporator Refrigerant
Pressure Ckt2
66
nvoEvapRfgtTmpC1
SNVT_temp_p
Evaporator Refrigerant
Temperature - Circuit 1
0.50°C
♥
Evaporator Saturated Rfgt
Temp Ckt1
67
nvoEvapRfgtTmpC2
SNVT_temp_p
Evaporator Refrigerant
Temperature - Circuit 2
0.50°C
♥
Evaporator Saturated Rfgt
Temp Ckt2
68
nvoCondRfgtPrsC1
SNVT_press_f
Condenser Refrigerant
Pressure - Circuit 1
30 KPA
♥
Condenser Refrigerant
Pressure Ckt1
69
nvoCondRfgtPrsC2
SNVT_press_f
Condenser Refrigerant
Pressure - Circuit 2
30 KPA
♥
Condenser Refrigerant
Pressure Ckt2
70
nvo-
CondRfgtTmpC1
SNVT_temp_p
Condenser Refrigerant
Temperature - Circuit 1
1.00°C or 3.00°C
6
♥
Condenser Saturated Rfgt
Temp Ckt1
71
nvo-
CondRfgtTmpC2
SNVT_temp_p
Condenser Refrigerant
Temperature - Circuit 2
1.00°C or 3.00°C
6
♥
Condenser Saturated Rfgt
Temp Ckt2
72
nvoAirFlowPctC1
SNVT_lev_percent
Air Flow Percent – Circuit
1
5.00%
♥
Air Flow Ckt1
73
nvoAirFlowPctC2
SNVT_lev_percent
Air Flow Percent – Circuit
2
5.00%
♥
Air Flow Ckt2
76
nvoHiSideOilPrsA
SNVT_press_f
High Side Oil Pressure -
Compressor A
20.0 kPa
♥
Oil Pressure - Compressor
1A
77
nvoHiSideOilPrsB
SNVT_press_f
High Side Oil Pressure -
Compressor B
20.0 kPa
♥
Oil Pressure - Compressor
1B
79
nvoHiSideOilPrsD
SNVT_press_f
High Side Oil Pressure -
Compressor D
20.0 kPa
♥
Oil Pressure - Compressor
2A
94
nvoRfgtDischTmpA
SNVT_temp_p
Refrigerant Discharge
Temperature -
Compressor A
0.50°C
♥
Discharge Temperature
Compressor 1A
95
nvoRfgtDischTmpB
SNVT_temp_p
Refrigerant Discharge
Temperature -
Compressor B
0.50°C
♥
Discharge Temperature
Compressor 1B
97
nvoRfgtDischTmpD
SNVT_temp_p
Refrigerant Discharge
Temperature -
Compressor D
0.50°C
♥
Discharge Temperature
Compressor 2A
100
nvoVoltageB
UNVT_3phase_volt
Voltage Per Phase –
Compressor B
defined at element
♥
SNVT_volt_ac
BC phase voltage
Note 1
Phase BC Voltage -
Compressor 1B
SNVT_volt_ac
CA phase voltage
Note 1
Phase CA Voltage -
Compressor 1B
SNVT_volt_ac
AB phase voltage
Note 1
Phase AB Voltage -
Compressor 1B
107
nvoCurrentB
UNVT_3phase_
current
Current Per Line –
Compressor B
defined at element
♥
SNVT_amp_ac
L1 current in Amps
Note 2
Line 1 Current -
Compressor 1B
SNVT_amp_ac
L2 current in Amps
Note 2
Line 2 Current -
Compressor 1B
SNVT_amp_ac
L3 current in Amps
Note 2
Line 2 Current -
Compressor 1B
SNVT_lev_percent
L1 current in %RLA
100%
Line 1 Current RLA -
Compressor 1B
SNVT_lev_percent
L2 current in %RLA
100%
Line 2 Current RLA -
Compressor 1B
SNVT_lev_percent
L3 current in %RLA
100%
Line 3 Current RLA -
Compressor 1B
112
nvoStartsRunTmA
UNVT_starts_runtime
Starts and Run Time –
Compressor A
defined at element
♥
SNVT_count_f
Starts
1
Starts Compressor 1A
SNVT_time_f
Run Time
360 sec
Running Time Compressor
1A