Start-Up
98
WSHP-SVX01W-EN
GEH*/GEV*150 (60 Hz)
GEH*/GEV*120 (50 Hz)
77
37.5
125-144
280-356
10-12
22-28
148-170
328-418
8-10
36-45
GEH*/GEV*150 (60 Hz)
GEH*/GEV*120 (50 Hz)
86
25.0
128-147
328-417
13-17
21-27
162-187
344-438
13-17
37-47
GEH*/GEV*150 (60 Hz)
GEH*/GEV*120 (50 Hz)
86
37.5
127-146
309-393
9-11
22-27
174-201
351-446
9-12
39-49
GEH*/GEV*150 (60 Hz)
GEH*/GEV*120 (50 Hz)
95
25.0
129-149
366-466
13-17
21-27
—
—
—
—
GEH*/GEV*150 (60 Hz)
GEH*/GEV*120 (50 Hz)
95
37.5
129-148
348-442
9-11
21-27
—
—
—
—
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
32
30.0
—
—
—
—
62-71
260-331
7-9
23-29
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
32
45.0
—
—
—
—
65-75
263-334
5-6
24-30
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
45
30.0
119-136
189-240
15-19
22-29
79-91
277-352
8-10
26-32
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
45
45.0
118-136
172-219
10-13
22-29
84-97
280-356
6-7
27-33
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
55
30.0
120-138
220-280
15-19
22-28
96-111
294-375
9-11
29-36
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
55
45.0
120-138
205-261
10-12
22-28
102-117
297-378
6-8
30-37
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
68
30.0
122-140
266-338
14-18
22-28
119-137
316-402
11-14
32-41
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
68
45.0
121-140
249-317
10-12
22-28
127-146
320-407
7-9
34-43
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
77
30.0
123-142
308-392
15-19
22-28
133-153
329-419
12-15
35-43
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
77
45.0
123-141
288-367
10-13
22-28
142-163
334-425
8-10
36-46
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
86
30.0
124-143
340-432
14-18
21-27
156-179
351-447
13-17
38-48
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
86
45.0
124-143
321-409
9-12
21-27
167-192
357-455
9-12
40-50
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
95
30.0
126-145
381-485
14-17
21-27
—
—
—
—
GEH*/GEV*180 (60 Hz)
GEH*/GEV*150 (50 Hz)
95
45.0
126-145
363-461
9-12
21-27
—
—
—
—
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
32
40.0
—
—
—
—
64-73
256-326
6-8
25-31
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
32
60.0
—
—
—
—
67-77
259-329
4-5
26-32
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
45
40.0
126-145
178-226
15-19
23-29
82-94
270-344
7-9
27-34
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
45
60.0
125-144
165-210
10-12
23-29
86-99
274-349
5-7
28-35
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
55
40.0
127-146
208-265
14-18
23-29
99-113
285-362
8-10
29-37
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
55
60.0
127-146
194-247
10-12
23-29
104-120
289-368
6-7
30-38
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
68
40.0
129-148
253-321
14-18
22-29
122-140
303-386
10-13
33-41
Table 54. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Model No.
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling
Heating
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
Summary of Contents for Axiom EXH Series
Page 123: ......