6
WSHP-SVX01W-EN
Digits 1, 2, 3 — Unit
Configuration
EXH=
High efficiency horizontal
EXV=
High efficiency vertical
Digit 4
—
Development Sequence
F
Digits 5, 6, 7 — Nominal
Capacity
006 =
0.50 Tons
009 =
0.75 Tons
012 =
1 Tons
015 =
1.25 Tons
018 =
1.50 Tons
024 =
2 Tons
030 =
2.50 Tons
036 =
3 Tons
042 =
3.50 Tons
048 =
4 Tons
060 =
5 Tons
070 =
6 Tons
Digit 8 — Voltage (Volts/Hz/
Phase)
1
=
208/60/1
2
=
230/60/1
3
=
208/60/3
4
=
460/60/3
7
=
265/60/1
8
=
230/60/3
Digit 9 — Heat Exchanger
1
=
Copper-water coil
2
=
Cupro-nickel water coil
7
=
Insulated copper water coil/
suction line
8
=
Insulated cupro-nickel water coil/
suction line
Digit 10 — Current Design
Sequence
Digit 11 — Refrigeration Circuit
0
=
Heating and cooling circuit
2
=
Heating and cooling circuit with
hot gas reheat
3
=
Heating and cooling circuit with
waterside economizer
Digit 12 — Blower Configuration
3
=
ECM motor
Digit 13 — Freeze Protection
A
=
20°F Freezestat (Extended range
geothermal)
B
=
35°F Freezestat
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B
=
Back supply-air arrangement
L
=
Left supply-air arrangement
R
=
Right supply-air arrangement
T
=
Top supply-air arrangement
Digit 16 — Return-Air
Arrangement
L
=
Left return-air arrangement
R
=
Right return-air arrangement
Digit 17 — Control Types
D
=
Deluxe 24V controls
B
=
Tracer® ZN524 controls
F
=
UC400
G
=
UC400 with wireless comm
Digit 18 — Tstat/Sensor Location
0
=
Wall mounted location
Digit 19 — Fault Sensors
1
=
Condensate overflow sensor
3
=
Condensate overflow and filter
maintenance timer
6
=
Condensate overflow and fan
status
J
=
Fan status, filter maintenance
timer and condensate overflow
sensor
Digit 20 — Temperature Sensor
0
=
No additional temperature sensor
1
=
Entering water sensor
Digit 21 — Insulation
1
=
Standard fiberglass insulation
2
=
Foil faced insulation in airstream
Digit 22 — Electric Heat
0
=
No electric heat
1
=
Internal boilerless electric heat
4
=
External boilerless electric heat
Digit 23 — ON/OFF Switch
0
=
No ON/OFF switch
1
=
ON/OFF switch (not available with
boilerless electric heat option)
Digit 24 — Filter Type
1
=
1-in. Throwaway filter
2
=
2-in. Throwaway filter
4
=
MERV 8
5
=
MERV13
Digit 25 — Acoustic
Arrangement
0
=
Enhanced sound attenuation
1
=
Deluxe sound attenuation
Digits 26, 27, 28, 29, 30, 31, 32,
33, 34 — Does not Apply to EXH
or EXV
00000000000= Digits 26, 27, 28, 29, 30, 31,
32, 33, 34 are not
applicable to the EXH or
EXV products
Digits 35 — Units Drain Pan
Option
A
=
Polymer drain pan
B
=
Stainless steel drain pan
Model Number Descriptions - 0.5 to 6 Tons