Installation
WSHP-SVX01W-EN
59
•
Near radiant heat (heat emitted from appliances or the
sun)
•
Near concealed pipes or chimneys
•
On outside walls or other non conditioned surfaces
•
In airflows from adjacent zones or other units.
Controls Using 24 Vac
Before installing any wire, refer to the electrical access
locations in the
of this manual.
Ensure that the AC control wiring between the controls
and the unit termination point does not exceed 3 Ohms/
conductor for the length of the run.
NOTICE
Component Failure!
Resistance in excess of 3 Ohms per conductor could
result in component failure due to insufficient AC
voltage supply.
Check all loads and conductors for grounds, shorts, and
mis-wiring. Use copper conductors unless otherwise
specified. Do not run the AC low-voltage wiring in the
same conduit with the high voltage power wiring.
Table 40. 24V AC conductors
Distance from unit to
control
Recommended wire size
000-460 ft
18 gauge
461-732 ft
16 gauge
733-1000 ft
14 gauge
Figure 56.
Low-voltage connection (GEH/V 0.5 to 5 ton
and EXH/V 0.5 to 6 ton equipment)
Deluxe Controls with Reheat
1TB1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
24 VAC
FAN
REVERSING VALVE (COOL)
COMPRESSOR
24 VAC COMMON & VAR SPD PUMP SOLENOID
24 VAC COMPRESSOR DISABLE INPUT
24 VAC COMPRESSOR DISABLE INPUT
HUMIDISTAT
VAR SPD PUMP SOLENOID
ALARM CONTACT OUTPUT
ALARM CONTACT OUTPUT
Deluxe Controls Wall Mounted Thermostat
1TB1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
24 VAC
FAN
REVERSING VALVE (COOL)
COMPRESSOR & VAR SPD PUMP SOLENOID
24 VAC COMMON & VAR SPD PUMP SOLENOID
ELECTRIC HEAT
24 VAC COMPRESSOR DISABLE INPUT
24 VAC COMPRESSOR DISABLE INPUT
ALARM CONTACT OUTPUT
ALARM CONTACT OUTPUT
Low-voltage connection diagrams for deluxe 24 V control
packages mounted on 0.5-6 ton equipment sizes are
shown in
Figure 57.
Low-voltage connection (GEH/V 6 to 25 ton)
Deluxe Controls with
-all Heat Pump Units w/ Reheat
using X13511090010 (T8511)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1TB2
24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1)
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
WATER ISOLATION VALVE
3RD STAGE HEAT (W3)
NOT USED
Deluxe Controls with
-all Heat Pump Units w/ Reheat
using X13511091010/X13511092010 (T7300)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1TB2
24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1)
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
WATER ISOLATION VALVE
3RD STAGE HEAT (W1)
NOT USED
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511090010 (T8511)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1TB2
24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
NOT USED
3RD STAGE HEAT (W3)
NOT USED
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511091010/X13511092010 (T7300)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1TB2
24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
NOT USED
3RD STAGE HEAT (W1)
NOT USED
Low-voltage connection diagrams for deluxe 24V control
packages for these thermostats mounted on 6-25 ton
equipment sizes are shown in
For controls using DC analog input/outputs, see
appropriate installation, operation and diagnostic
manuals for connection, CNT-SVX11*-EN (ZN524). For
installation, operation and programming see BAS-
SVX065*-EN (UC400).
Blower Motor Speed-Tap Retrofit
Note:
For GEH/V 0.5 to 5 ton units only.
Motors installed in the unit include 4-speed or 3-speed
configurations. All voltages include a 4-speed
configuration, with the exception of 380V, 415V, 460V
which contain a 3-speed arrangement and 575V which
contains a 2-speed arrangement. To modify the rpm of the
motor, the following steps must be followed.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.
Summary of Contents for Axiom EXH Series
Page 123: ......