8.5.6 Error output
Definition of the data value, which is transmitted if an error is present. The data value
is output, if the laser can output no more measurement. This is given e.g., if a beam
interruption is present.
Availability
TR-Mode
X
TR-Mode extended
X
Selection
Description
Default
Last correct
value
Output of the last valid position
X
Error output
value
Output of the value, which was defined under the
parameter
Error output value
, see page 120.
8.5.7 Min current
Definition, which minimum analog current shall be output.
Availability
TR-Mode
TR-Mode extended
X
not supported!
Selection
Description
Default
0 mA
Current range: 0…20 mA
X
4 mA
Current range: 4…20 mA