Typical Test Results
Actual test results vary depending on the equipment under
test. TPI recommends you check with the manufacturer of the
equipment being tested to determine specific acceptable
results.
Oxygen
3% to 6%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
300
°F
to 500
°F
Draft
-0.15 inH2O
Oxygen
4% to 7%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
325
°F
to 625
°F
Draft
-0.15 inH2O
Power Burners (Gas Fired)
Power Burners (Oil Fired)
Oxygen
7% to 9%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
325
°F
to 500
°F
Draft
-0.15 inH2O to -0.4 inH2O
Gas Fired Burners (Atmospheric / Fan Assist)