background image

ENGLISH

6

9. NOTE FOR MAINTENANCE WORK

1.  Checks to the area

Prior to beginning work on systems containing flammable re-
frigerants, safety checks are necessary to ensure that the risk 
of ignition is minimised. For repair to the refrigerating system, 
the following precautions shall be complied with prior to con-
ducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as 
to minimise the risk of a flammable gas or vapour being pres-
ent while the work is being performed.

2.  General work area

All maintenance staff and others working in the local area shall 
be instructed on the nature of work being carried out. Work in 
confined spaces shall be avoided. The area around the work-
space shall be sectioned off. Ensure that the conditions within 
the area have been made safe by control of flammable material.

3.  Checking for presence of refrigerant

The area shall be checked with an appropriate refrigerant detec-
tor prior to and during work, to ensure the technician is aware of 
potentially flammable atmospheres. Ensure that the leak detec-
tion equipment being used is suitable for use with flammable re-
frigerant, i.e. nonsparking, adequately sealed or intrinsically safe.

4.  Presence of fire extinguisher

If any hot work is to be conducted on the refrigeration equip-
ment or any associated parts, appropriate fire extinguishing 
equipment shall be available to hand. Have a dry powder or 
CO2 fire extinguisher adjacent to the charging area.

5.  No ignition sources

No person carrying out work in relation to a refrigerant system 
which involves exposing any pipe work that contains or has 
contained flammable refrigerant shall use any sources of igni-
tion in such a manner that it may lead to the risk of fire or explo-
sion. All possible ignition sources, including cigarette smoking, 
should be kept sufficiently far away from the site of installation, 
repairing, removing and disposal, during which flammable re-
frigerant can possibly be released to the surrounding space. 
Prior to work taking place, the area around the equipment is to 
be surveyed to make sure that there are no flammable hazards 
or ignition risks. ”No Smoking” signs shall be displayed.

6.  Ventilated area

Ensure that the area is in the open or that it is adequately venti-
lated before breaking into the system or conducting any hot 
wok. A degree of ventilation shall continue during the period 
that the work is carried out. The ventilation should safely dis-
perse any released refrigerant and preferably expel it externally 
into the atmosphere.

7.  Checks to the refrigeration equipment

Where electrical components are being changed, they shall be 
fit for the purpose and to the correct specification. At all times 
the manufacturer’s maintenance and service guidelines shall be 
followed. If in doubt consult the manufacturer’s technical de-
partment for assistance.
The following checks shall be applied to installations using 
flammable refrigerants:
- the charge size in accordance with the room size within which 

the refrigerant containing parts are installed;

- the ventilation machinery and outlets are operating adequately 

and are not obstructed.

8.  Checks to electrical devices

Repair and maintenance to electrical components shall include 
initial safety checks and components inspection procedures. If 
a fault exists that could compromise safety, then no electrical 
supply shall be connected to the circuit until it is satisfactorily 
dealt with. If the fault cannot be corrected immediately but it is 
necessary to continue operation, an adequate temporary solu-
tion shall be used. This shall be reported to the owner of the 
equipment so all parties are advised.
Initial safety checks shall include:
- that capacitors are discharged: this shall be done in a safe 

manner to avoid possibility of sparking;

- that there no live electrical components and wiring are ex-

posed while charging, recovering or purging the system;

- that there is continuity of earth bonding.

9.  Repairs to sealed components

During repairs to sealed components, all electrical supplies 
shall be disconnected from the equipment being worked upon 
prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to 
equipment during servicing, then a permanently operating form 
of leak detection shall be located at the most critical point to 
warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that 
by working on electrical  components, the casing is not altered 
in such a way that the level of protection is affected. This shall 
include damage to cables, excessive number of connections, 
terminals not made to original specification, damage to seals, 
incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such 
that they no longer serve the purpose of preventing the ingress 
of flammable atmospheres, Replacement parts shall be in ac-
cordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of 

some types of leak detection equipment. Intrinsically safe 
components do not have to be isolated prior to working on 
them.

10. Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to 
the circuit without ensuring that this will not exceed the permis-
sible voltage and current permitted for the equipment in use.
Intrinsically components are the only types that can be worked 
on while live in the presence of a flammable atmosphere. The 
test apparatus shall be at the correct rating.
Replace components only with parts specified by manufactur-
er. Other parts may result in the ignition of refrigerant in the at-
mosphere from a leak.

11. Cabling

Check that cabling will not be subject to wear, corrosion, ex-
cessive pressure, vibration, sharp edges or any other adverse 
environmental effects. The check shall also take into account 
the effects of aging or continual vibration from sources such as 
compressors or fans.

12. Leakage detection for flammable refrigerants

Under no circumstances shall potential sources of ignition be 
used in the searching for or detection of refrigerant leaks. A ha-
lide torch (or any other detector using a naked flame) shall not be 
used.

13. Leak detection methods

The following leak detection methods are acceptable for sys-
tems containing flammable refrigerant.
Electronic leak detectors shall be used to detect flammable re-
frigerants, but the sensitivity may not be adequate, or may 
need recalibration (Detection equipment shall be calibrated in a 
refrigerant-free area). Ensure that detector is not a potential 
source of ignition and is suitable for the refrigerant used.
Leak detection fluids are suitable for use with most refrigerants 
but the use of detergents containing chlorine shall be avoided 
as the chlorine may react with the refrigerant and corrode the 
copper pipe-work.
If a leak is suspected, all naked flames shall be removed/extin-
guished.
If a leak of refrigerant is found which requires brazing, all of the 
refrigerant shall be recovered from the system. Oxygen free ni-
trogen (OFN) shall then be purged through the system both be-
fore and during the brazing process.

14. Removal and evacuation

When breaking into the refrigerant circuit to make repairs-or for 
any other purpose-conventional procedures shall be used.
However, it is important that best practice is followed since
Flammability is a consideration. The following procedure shall
be adhered to:
Remove refrigerant;
Purge the circuit with inert gas;
Evacuate;
Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct re-
covery cylinders. The system shall be “flushed” with OFN to 
render the unit safe. This process may need to be repeated 

Summary of Contents for TD-C1416

Page 1: ...FTAVFUKTARE OSUSZACZ OPERATING MANUAL ENGLISH P 1 MANUAL D UTILISATION FRANÇAIS P 9 BEDIENUNGSANLEITUNG DEUTSCH P 17 GEBRUIKSAANWIJZING NEDERLANDS P 25 MANUALE DI ISTRUZIONI ITALIANO P 33 MANUAL DE INSTRUCCIONES ESPAÑOL P 41 MANUAL DE INSTRUÇÕES PORTUGUÊS P 49 BETJENINGSVEJLEDNING DANSK P 57 BRUKSANVISNING SVENSKA P 65 INSTRUKCJA OBSŁUGI POLSKI P 73 ...

Page 2: ...he appliances can be used indoor but not in laundry rooms 3 Do not set the unit close to heat gener ating devices or near flammable and dangerous materials 4 Never put your fingers or objects into the intake or discharge ducts 5 Do not sit or stand on the unit 6 Discard water that has collected in the tank as required 7 Do not operate the dehumidifier in a closed area such as inside a closet as it...

Page 3: ...e shall be compliance with national gas regulations Servicing shall be performed only as rec ommended by the manufacturer The appliance shall be stored so as to prevent mechanical damage from occur ring Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessment authority which authorises their com...

Page 4: ...indoor air dry and comfortable Lightweight Portable Design The dehumidifier is built to be compact and lightweight The cast ers on the bottom of the unit make it easy to move from room to room Low Temperature Operation with Automatic Defrost When the unit is running in a room temp between 7 C and 12 C it will be stop to defrost for every 30 minutes When the unit is running in a room temp between 1...

Page 5: ...shutdown time from 1 to 24 hours Once turned on or off by user or entering water full state the unit may lost the timing function 4 DRAINING THE COLLECTED WATER When the drainage tank is full the tank full indicator light will turn on the operation will stop automatically and the buzzer will beep 15 times to alert the user that the water need to be emptied from the drainage tank 5 EMPTYING THE DRA...

Page 6: ...n in the left drawing 8 TROUBLESHOOTING If a condition listed below occurs please check the following items before calling customer service Problem Possible Cause Solution The unit doesn t operate Has the power cord been disconnected Plug the power cord into the outlet Is the tank full indi cation lamp blink ing The tank is full or in a wrong posi tion Empty the water in the drainage tank and then...

Page 7: ...e no live electrical components and wiring are ex posed while charging recovering or purging the system that there is continuity of earth bonding 9 Repairs to sealed components During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to ...

Page 8: ...s sioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 18 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only ap...

Page 9: ...ry in basis to your nearest autho rized dealer or distributor of TOYOTOMI WHAT YOU MUST DO FOR WARRANTY SERVICE You must return the defective Product or part to any authorized dealer or distributor of TOYOTOMI with this LIMITED WARRANTY If ser vice is not available locally please contact our CUSTOMER RELATIONS DEPARTMENT at TOYOTOMI EUROPE SALES B V E MAIL info toyotomi eu INTERNET www toyotomi eu...

Page 10: ... TOYOTOMI EUROPE SALES ITALY S R L VIA T EDISON 11 20875 BURAGO DI MOLGORA MB ITALY Email info toyotomi it http www toyotomi it TOYOTOMI EUROPE SALES SPAIN S A CALLE TRIGO 9 BAJO 2 28914 LEGANÉS MADRID SPAIN Email info toyotomi es http www toyotomi es TOYOTOMI FRANCE S A S LA CARTONNERIE RUE DU CANAL 27500 PONT AUDEMER FRANCE Email info toyotomi eu http www toyotomi eu New 03 20 Printed in P R C ...

Reviews: