Electrical Control Function
Electrical Control
Compact cassette:
1.3.2.3 Low evaporator coil temperature T2 protection
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for 3 minutes, the compressor and outdoor fan will
shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
1.3.2.4 Condenser high temperature T3 protection
T3
TE12
Off
On
TE13
When T3
≥
TE12 for Time1, the compressor will shut off. When T3
<
TE13,the compressor will restart.
T1-TS
4
°
C High
1
°
C Low
T1-TS
3
°
C High
1
°
C Low