2. Modified coefficient table of ambient condition power.
The conditions of generator rated output:
Altitude:
≤
1000m / Ambient temperature: 5 ~ 25°C / Relative Humidity: 30 %
Ambient modified coefficient: C (Relative humidity 30%)
Note:
When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P=5KW, altitude is 1000m, ambient temperature is 35°C,
relative humidity is 80%, the rated power of generator is:
P = Pn x (C-0.02) = 5 x (1.0
– 0.02) = 4.9 kW
Summary of Contents for TDWG12000CXE-N
Page 1: ...1 ...
Page 13: ...13 7 THE FUNCTIONS OF THE DIGITAL PANEL OPERATION PANEL ...
Page 17: ...17 9 MALFUNCTION AND COUNTERMEASURES 1 Maintenance Schedule ...
Page 20: ...20 2 Judge and eliminate trouble ...
Page 21: ...21 ...
Page 22: ...22 Controller Troubleshooting ...
Page 23: ...23 11 ELECTRICAL DIAGRAM 1 Single Phase TDWG12000CXE N TDWG12000SGE N ...
Page 24: ...24 2 Three Phase TDWG12000CXE3 N TDWG12000CXE3D N TDWG12000SGE3 N TDWG12000SGE3D N ...
Page 44: ...44 11 DIAGRAMA ELÉTRICO 11 1 Monofásico TDWG12000CXE N TDWG12000SGE N ...
Page 45: ...45 11 2 Trifásico TDWG12000CXE3 N TDWG12000CXE3D N TDWG12000SGE3 N TDWG12000SGE3D N ...
Page 56: ...56 PANEL DE OPERACIONES ...
Page 59: ...59 9 M ALFUNCIONES Y COMO CONTRARESTARLAS ...
Page 60: ...60 ...
Page 62: ...62 2 Chequee y elimine problemas ...
Page 63: ...63 ...
Page 64: ...64 Problemas con el controlador 11 DIAGRAMA DE CABLEADO ELECTRICO 11 1 Monofásico ...
Page 65: ...65 TDWG12000CXE N TDWG12000SGE N 11 2 Trifásico ...
Page 72: ...72 ...
Page 73: ...73 TY_TDWG12000CX SG_MA_R00 ...
Page 74: ...74 ...