15
2. Frequency Protection:
50Hz (45~55)Hz
60Hz (55~65)Hz
When the set value is exceeded, frequency LED starts flashing; after 7 ,seconds delay in case of
under frequency and 3 seconds delay in case of over frequency , alarm shutdown is initiated. After
that frequency LED continues to flash and shows pre-alarm value.
3. Overload Protection
If the set value is exceeded by 5% or less, alarm will not be initiated;
If the set value is exceeded by more than 5%, power LED will start flashing;
If the set value is exceeded by 5-7.5% and continuous for more than 3 hours, then alarm shutdown
will be initiated;
If the set value is exceeded by 7.5-10% and continues for more than 1 hours, alarm shutdown will
be initiated;
If the set value is exceeded by more than 10%, the gen-set will be shut down immediately
(approximately 2 seconds);
After alarm shutdown is initiated power LED continues to flash and shows pre-alarm value.
4. Low Oil Pressure Protection
Irrespective of whether auto protection mode is enabled or not, low oil pressure will lead to
automatic disconnection of oil circuit; 5 High engine temperature protection.
If engine temperature exceeds 108
, LED window starts flashing; after 7 second delay , protection
begins; LED window continues to flash and shows pre-protection value (for air-cooled engine);
5. High Engine Temperature Protection
If engine temperature exceeds 98
, LED window starts flashing; after 7 second delay, protection
begins; LED window continues to flash and shows pre-protection value (for air-cooled engine);
NOTE:
During Safety On delay, protection is disabled; after Safety On Delay, when voltage,
frequency, overload, high temperature protection is initiated, fuel output deactivates.
WARNING:
When the engine is running, start battery must not be removed.
Summary of Contents for TDWG12000CXE-N
Page 1: ...1 ...
Page 13: ...13 7 THE FUNCTIONS OF THE DIGITAL PANEL OPERATION PANEL ...
Page 17: ...17 9 MALFUNCTION AND COUNTERMEASURES 1 Maintenance Schedule ...
Page 20: ...20 2 Judge and eliminate trouble ...
Page 21: ...21 ...
Page 22: ...22 Controller Troubleshooting ...
Page 23: ...23 11 ELECTRICAL DIAGRAM 1 Single Phase TDWG12000CXE N TDWG12000SGE N ...
Page 24: ...24 2 Three Phase TDWG12000CXE3 N TDWG12000CXE3D N TDWG12000SGE3 N TDWG12000SGE3D N ...
Page 44: ...44 11 DIAGRAMA ELÉTRICO 11 1 Monofásico TDWG12000CXE N TDWG12000SGE N ...
Page 45: ...45 11 2 Trifásico TDWG12000CXE3 N TDWG12000CXE3D N TDWG12000SGE3 N TDWG12000SGE3D N ...
Page 56: ...56 PANEL DE OPERACIONES ...
Page 59: ...59 9 M ALFUNCIONES Y COMO CONTRARESTARLAS ...
Page 60: ...60 ...
Page 62: ...62 2 Chequee y elimine problemas ...
Page 63: ...63 ...
Page 64: ...64 Problemas con el controlador 11 DIAGRAMA DE CABLEADO ELECTRICO 11 1 Monofásico ...
Page 65: ...65 TDWG12000CXE N TDWG12000SGE N 11 2 Trifásico ...
Page 72: ...72 ...
Page 73: ...73 TY_TDWG12000CX SG_MA_R00 ...
Page 74: ...74 ...