Exterior wall opening:
Determine the exact position of the Heli-Fire so that the venting pipe is centered between two building
framing members. Consult your local building codes prior to proceeding.
IMPORTANT: When locating the opening, it should be noted that venting terminal clearances
must be maintained. See “Vent Terminal Minimum Clearances” & “Power Venting
Clearances” on page 26 for proper clearances.
Note: When using a surface mount power vent on a flat roof, the power vent must be attached
atop an elevated platform in order to keep it clear of snow and water accumulations .
Use only pipe supplied with the power vent kits and extension kits.
Flexible aluminum
venting
Combution
air Inlet
surface
mount
power
vent
flush
mount
power
vent
Maximum flue outlet pipe length is
50 feet and the maximum
combustion air inlet pipe is 50 feet.
Minimum venting
length is 1.5’ to
the power vent
Direction
of air flow
Direction
of air flow
stud / vent supports
Flat roof configuration
Peaked roof configuration
Recommended elevated platform
(min. 12” high. Check local codes).
location
option
surface
mount
power
vent
Outlet dir
ection (Riser not r
equired)
Surface mount power vent
stud / vent supports
Figure 34: Heli-Fire Venting configurations.