LINE
NEUTRAL
GND
WHT GND
WHT
BK - BLACK
BRN - BROWN
GND - GROUND
GRY - GREY
WHT - WHITE
WHT
BK
GRY
BK
BRN
BRN
BRN
BRN
GND
BK
Figure 29: Wiring instructions.
Installers Information
Electrical Connection
The Heli-Fire requires unswitched
electrical power supply. The fire
feature including its power vent
are rated at 115 Volts, 60 Hz, 2.48
amps.
•
Connect electrical power
supply to the black and white
wires inside the electrical
connections compartment as
shown in Fig.
•
Connect the ground wire to the
green wire inside the compart-
ment (Figure 29).
•
Connect the Town and Country
On/Off wall switch (supplied) to
the two brown wires.
Heli-Fire electrical connection
Power vent electrical
connection
•
Connect the black wire from
the power vent to the grey wire
inside the electrical connection
compartment.
•
Connect the white wire from
the power vent to the white
wire inside the compartment.
•
Connect the ground wire
to the green wire inside the
compartment.