Optional module for electric lock/magnetic clamp
• The control unit needs an optional module for connec-
tion of an electric lock/magnet (12V or 24Vd.c. version
depending on electric lock).
Connection of module
•
ATTENTION: turn off power supply!
• The module is also housed in the control cabinet - fixed
at positions
(P1)
by spacers and screws.
• Connect electric lock module via RJ-plug
(E)
with the
control unit
.
• Connect the electric lock (12/24Vd.c.) to the removable
terminals
72/73
of the module.
• The magnet (24Vd.c.) must be connected via a resistor
(R)
for the connection to the module.
• To do this, push the connecting cable of the magnetic clamp
as shown into the opening of the series resistor and fix by
means of crimping pliers.
• Connect the connection cable and resistor
(R)
, as shown,
to the removable terminals
74 (–) / 75 (+)
of the module.
Pay attention to polarity.
• To supply the module the 2-pin cable is connected to the
control terminals
(VE).
• After wiring, the E-lock-mode has still to be activated in
the menu of the control under („peripherals / locking“
and „peripherals / electric lock“)
• Magnets are driven into the open and closed position of
the gate, the electric lock only in closed position.
The series resistor (R) is for tousek
magnets GD 50 and GD 70.
E
P1
VE
– +
electric lock
12 or 24Vd.c
magnet
24Vd.c
R
fix
24V
Danger
•
Before connection works or taking off the housing cover the power supply has to be turned off !
•
Follow safety instructions!
(
page 5)
optional dropbolt module
• In order to connect the dropbolt SAFELOCK to the control
unit it needs an optional modul and a dropbolt control unit.
If needed then for double leaf swing gate also two dropbolts
can be connected. Thereby the terminal block is labelled
with
„X“
for the first bolt and with
„Y“
for the second bolt.
Modul connection
•
ATTENTION: Turn off the power supply!
• The module
(E)
is connected with a RJ-plug-in connector
to the control unit
(ST)
in the housing of the ST 63.
• The removable terminals „X“ and „Y“ on the module are
wired to the dropbolt control unit (MST) according to the
sketch (
page 27).
• After succesful connection the dropbolt operation need to
be activated in the control unit menu („peripherials/locking“
and „peripherials/dropbolt“)
E
Control unit ST63 in steel cabinet with integrated
dropbolt module
(E),
dropbolt control unit
(MST)
MST
ST
E