ENGLISH
ADJUSTING MAXIMUM OUTLET TEMPERATURE
ADJUSTING OUTLET TEMPERATRURE
ACCESSING ANG CLEANING THE VALVE
1. Shut the water off at the stop valves.
2. To decrease temperature:
Remove cap and screw and pull handle slowly to remove.
Turn handle counter-clockwise one notch and reinstall onto cartridge.
To increase temperature:
Remove cap and screw and pull
handle slowly to remove.
Turn handle clockwise one notch
and reinstall onto cartridge.
3. Secure handle with screw and cap.
4. Open shut off valve.
5. Check water temperature.
**Repeat steps 1-5 if necessary
1. To decrease temprature:
Turn handle clockwise.
2. To increase temprature:
Turn handle counter-clockwise.
1. Shut the water off at the stop
valves.
2. Disconnect supply hoses.
3. Pull out the strainer and clean it
with a brush.
4. Reinstall the clean strainer and
connect water supply hoses.
5. Open the stop valves.
- 5 -
Handle
Screw
Cap
Strainer
Strainer
Strainer
Brush
ENGLISH
INSTALLATION PROCEDURE
CAUTION: RISK OF PERSONAL INJURY.
This valve requires the maximum outlet temperature to be set/adjusted by the
installer.
The maximum outlet water temperature should never exceed 120 ºF (49 °C).
1. Turn off the main water supply.
2. Connect the hot water supply to the inlet marked "H" and the cold water supply
to the inlet marked "C".
- 4 -
or
Controller
Supply hose
Thermostatic mixing valve
mounting bracket
Supply hose
Supply hose
Angle stop
G1/2
G1/2
Angle stop
Thermostatic mixing valve
Swivel coupling
G1/2 compatible with 1/2 NPSM
ONLY THERMOSTATIC MIXING VALVE INCLUDED