DC Inverter U-match Series Cassette Type Unit
21
4.5.4 Testing of Drain Piping
After piping work is finished, check if drainage flows smoothly.
Shown in the Fig.32, Add approximately 1liter of water slowly into the drain pan and check
drainage flow during COOL running.
Drain hose
Test hole cover
Test hole
<Immiting water from the rest hole>
Plastic water pot (The length of
the pipe should be about 100mm.)
<Immiting water from the outlet vent terminal>
Above 100mm
Drain vent for repair use (plastic stopper
is included) (drain the water in waterspoit
by this outlet vent)
Fig.32
4.6 The Panel Installation
4.6.1 Precautions
(1).
See the figure below for the relationship of the front panel and the connecting pipe.
The connecting
pipe should be located
corresponding to
the marking.
Fig.33
(2). Improper screwing of the screws may cause the troubles shown in Fig.34.
Condensate
Fig.34
Summary of Contents for TKH12K3FI
Page 36: ......