4.15 DIGITAL I/O SMS ALERT
Supported models: Lock 500, TOSIBOX
®
670 and TOSIBOX
®
675.
In order for the SMS alert feature to work, make sure to use
a SIM card that supports sending SMS messages.
SMS alert feature can be activated on Digital I/O settings by
selecting “Send SMS” for “Input port 1 role” and/or “Input
port 2 role”. After this, more settings for the SMS alert
feature will become visible.
The following settings need to be defined for input port 1 or
input port 2 or both:
Input port ≤X≥ SMS action
Select the trigger (high / low) for SMS sending: “Send message
when input ≤X≥ is high” or ”Send message when input ≤X≥ is
low”
Input port ≤X≥ SMS message
Define the message to be sent. Concatenated SMS is not
supported so the maximum length of a message is 160
characters (western alphabet). If using non-western alphabet,
the limit is 70 characters.
Input port ≤X≥ SMS phone numbers
Enter phone number(s) to send the message to. Only one
number per input field is allowed. More phone numbers can be
added by adding a new input field.
Input port ≤X≥ SMS send limit
Determines how many messages per minute will be sent. “0”
stands for no limit. Use this feature when the I/O may switch
high-low several times and you do not want to send SMS for
each state change.
Any message sent will be sent to all numbers defined in “Input
port ≤X≥ SMS phone numbers”
Input port ≤X≥ SMS target modem
Currently only internal modem is supported. In case there
are two SIMs inserted, the SMS will be sent from the active
SIM at the time of the alarm.
Both I/O ports have SMS settings independent of each