WX9 ASD Installation and Operation Manual
89
Input Terminal 4 (RES) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
RES
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F143
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 5-8 (S1-S4) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
S1 – S4
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 9-16 (S5-S12) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
S5 – S16
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 On Delay
Program
Terminal
Output Terminal Delays
Once the condition is met to close the
OUT1
(
A
&
C
) output terminals, this
parameter delays the closing of the terminals by the programmed value.
For example, if
the
OUT1
function is programmed as
Over-Torque Alarm
,
OUT1
will close 2.0 mS (the default value for OUT1 On Delay) after the over-
torque condition occurs.
The delay may be increased to prevent relay chatter.
Direct Access Number — F150
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......