18
17
Terminal functions
Standard connection diagrams
+DC -DC
PO
MC
MCCB
R/L1
S/L2
T/L3
RO
SO
TO
U/T1
Motor
V/T2
W/T3
+SU
FM
(OUT1)
AM CCA
RX VI/II RR/S4 PP
P24/PLC
OUT1
OUT2
NO
CC
FLB
FLC
FLA
PA/+
PC/-
PB
IM
400/200 V transformer
(400 V class only)
Control power supply
backup (optional)
NC contact of
overload relay
Surge killer
MC
RUN
RUN
ON
RUN
OFF
F
R
ST
RES
S1
S2
Ammeter or voltmeter
Voltage signal: -10 to +10 V
Voltage signal: 0 to 10 V
or current signal: 4 (0) to 20 mA
External potentiometer
(or voltage signal across RR/S4-CCA terminals:
0 to 10 V input)
S3
CC
Forward run signal
Reverse run signal
Stand by
Reset
Preset speed 1
Preset speed 2
Preset speed 3
Common
RY
RY
Frequency
meter
Ammeter
(a)
(a)
(a)
(a)
(a)
0-10V
0-20mA
0-1mA
FM
S4
RR
RR/S4
SW2
SW3
PLUS
LO
OUT1
SW4
SW1
SOURCE
INT/PLC PLC INT
SINK
F
actor
y def
ault settings
Main circuit power supply
200 V class:
0.4 to 55 kW
3-phase, 200 to 240 V - 50/60 Hz
75 kW
3-phase, 200 to 240 V - 50 Hz
3-phase, 200 to 240 V - 60 Hz
400 V class:
0.75 to 90 kW
3-phase, 380 to 480 V - 50/60 Hz
110 to 500 kW 3-phase, 380 to 440 V - 50 Hz
3-phase, 380 to 480 V - 60 Hz
*1
*4
*2
*8
*9
*10
*9
*9
*11
*7
*5
*4
*6
From (a)
*1: The inverter is shipped with the terminals PO and PA/+ shorted with a bar (200V-45kW or smaller, 400V-75kW or smaller).
Remove this shorting bar when installing a DC reactor (DCL).
For 200 V - 55 kW or more, and 400 V - 90 kW or more models, be sure to install the DC reactor.
*2: The DC reactor is built in for models 200V-11kW~45kW and 400V-18.5kW~75kW.
*3: The noise filter is built in for models 200V-45kW or smaller and all of 400V.
*4: External braking resistor (option). Dynamic braking drive circuit built-in (GTR7) as standard for models 160kW or smaller.
*5: Power generation braking Unit (option). When the external braking resistor (optional) is used on 200 kW or more models, the separate power braking unit (optional) is required.
*6: To supply a DC power, connect the cables to the PA/+ and PA/- terminals.
*7: If you want to use a DC power supply to operate the inverter (200V: 18.5kW or more, 400V: 22kW or more), be sure to contact your supplier customer support center, because an
inrush current limiting circuit is required in such a case.
*8: For models 200V-75kW and 400V-110kW or larger, three-phase power input is necessary to drive the fan if you want to use a DC power supply.
*9: The functions assigned to terminals OUT1, VI/VII and RR/S4 can be switched by changing parameter settings.
*10: To supply control power from an external power supply for backing up the control power supplied from the inverter, an optional control power backup device (CPS002Z) is
required. In such a case, the backup device is used at the same time with the internal power supply of the inverter.
*11: The optional control power backup unit can be used with both 200V and 400V models.
Main
circuit
Control
circuit
Noise
filter
Fan
*3
■
Main circuit terminal
■
Control circuit terminal
The terminal function settings can be changed according to the application.
*1: Although the CC terminal and the CCA terminal are not insulated, they should be used separately, one for the logic circuit and the other for the analog circuit.
Terminal Symbol
Terminal Function
Grounding terminal for inverter casing
200V class: 400V class:
0.4~45kW Three-phase 200~240V-50/60Hz
55kW, 75kW Three-phase 200~220V-50Hz
Three-phase 200~240V-60Hz
Connect to a (3-phase induction) motor.
Connect a braking resistor. (For the optional dynamic braking unit, connect it between PA/+ and PC/-.)
Change the parameters , and if necessary.
200kW models and smaller are not equipped with terminal PB. If your are using such a model and you wish to use a braking resistor, you will need
to purchase a braking unit separately.
This is a negative potential terminal in the internal DC main circuit. DC common power can be input across the PA/+ terminals (positive potential).
Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a short bar when shipped from the factory (200V: 45kW or
smaller, 400V: 75kW or smaller). Before installing DCL, remove the short bar.
200V class: 75kW
400V class:110kW~500kW
Inverter’s cooling power input terminals. When using a DC power supply, connect three-phase power cables.
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
PA/+, PB
PC/-
PO, PA/+
RO, SO, TO
0.75~75kW Three-phase 380~480V-50/60Hz
90~500kW Three-phase 380~440V-50Hz
Three-phase 380~480V-60Hz
F
R
ST
RES
S1
S2
S3
RR/S4
P24/PLC
CC*
1
PP
RR/S4
VI/I I
RX
FM
AM
OUT1
OUT2
NO
CCA*
1
+SU
FLA
FLB
FLC
Terminal Symbol
Function
Electrical Specifications
Input/output
Lan current signal. Choose low current contacts to avoid
poor attaching.
Source input
ON : DC11V or more
OFF : Less than DC5V
Input
Input
Input
Input
Input
Input
Input
Input
Output
Input
Output
Input
Input
Input
Output
Output
Output
Input
Output
Multifunction prog
rammab
le contact input
Voltage free contact input 24Vdc-5mA or less
* Sink/source selectable with SW1
Sink input
ON : Less than DC10V
OFF : DC16V or more
Note:
Even when an external power supply is used (in sink logic
mode, i.e., when SINK (PLC) is selected), connect the
reference potential-side (0V side) cable from the power supply
to the CC terminal.
10Vdc (Permissible load current:10mAdc)
250Vac-2A
30Vdc-1A
:at resistance load
250Vac-1A
:cosF=0.4
10Vdc (Internal impedance:30 k
Ω
)
10Vdc (Internal impedance:30 k
Ω
)
4~20mA (Internal impedance:242
Ω
)
10Vdc (Internal impedance:22 k
Ω
)
1mA full-scale DC ammeter or 7.5Vdc-1mA
full-scale DC voltmeter
0-20mA (4-20mA)
Full-scale DC ammeter
1mA full-scale DC ammeter or 7.5Vdc-1mA
full-scale DC voltmeter
Open collector output
24Vdc-50mA
*Sink logic/source logic switchable
Voltage:24Vdc
±
10%
Use a power supply with a current rating of 1.1A or more.
—
Shorting across F-CC causes forward rotation; open causes deceleration stop.
(Across ST-CC is short state.)
Shorting across R-CC causes reverse rotation; open causes deceleration stop.
(Across ST-CC is short state.)
The motor is on standby if ST and CC are connected. It coasts to a stop if this connection
is broken. This terminal can be used for interlocking.
Shorting and then opening RES-CC cancels the status held by an inverter protective
function. When the inverter is operating normally, shorting and then opening RES-CC
produces no effect.
Shorting across S1-CC causes preset speed operation.
Shorting across S2-CC causes preset speed operation.
Shorting across S3-CC causes preset speed operation.
SW3: When SW4 is in the S4 position, S4 and CC are shorted and preset speed operation
is selected.
24Vdc power output (when SW1 is in any position other than PLC)
24V internal output terminal
If SW1 is turned to the PLC position, this terminal can be used as a common terminal when an
external power supply is used.
Digital signal equipotential (0V) terminal for the control circuit and equipotential (0V) terminal
for an optional control power supply backup.
Analog input setting power output
SW3: Multifunction programmable analog input terminal when SW4 is in the RR position.
Standard default setting:0~10Vdc input and 0~60Hz frequency.
Multifunction programmable analog input.Standard default setting: 0~10Vdc input and 0~60Hz
frequency. This terminal can also be used as a 4-20mAdc (0-20mAdc) input terminal, if the
parameter set to 1.
Multifunction programmable analog input. Standard default setting:0~
±
10Vdc input and
0~
±
60Hz frequency.
Multifunction programmable analog output. Standard default setting: output frequency
Connect a 1mAdc full-scale ammeter or 7.5Vdc (10Vdc)-1mA full-scale voltmeter.
This terminal can also be used as a 0-20mAdc (4-20mA) terminal, if the parameter set to
1 and the SW2 switch is set to OFF.
Multifunction programmable analog output. Standard default setting: output current
Use this terminal to connect a 1mAdc full-scale ammeter or 7.5Vdc (10Vdc)-1mA full-scale
voltmeter.
Multifunction programmable open collector output. The default setting is to output a signal when
output low speed threshold has been reached. Depending on the SW4 setting, pulses are
output with frequencies of 1.00kHz to 43.20kHz. Standard default setting:3.84kHz
Multifunction programmable open collector output. By default, it is set to output a signal
indicating the completion of acceleration or deceleration.
Digital output signal equipotential (0V) terminal for the control circuit. It is insulated from the CC terminal.
Analog input/output signal equipotential (0V) terminal for the control circuit.
DC power input terminal for operating the control circuit. Connect a control power backup
device (optional) bSU and CC.
Relay contact output. Contact rating
Used to detect the activation of the inverter's protective function. Contact across FLA-FLC is
closed and FLB-FLC is opened during protection function operation.
Common to
input/output
24Vdc-200mA
—
—
Common to
input/output