3. Installing the IPE001Z
Install the EtherNet/IP™ option to
VF-AS1/PS1
as follows.
*When this option is used together with the IO card option, attach this option to the front panel
side.
Mandatory
Turn off the input power of VF-AS1/PS1 and wait for at least 15 minutes and then
check that the CHARGE lamp on VF-AS1/PS1 is no longer lit.
(1) Turn off input power of VF-AS1/PS1 and wait for at least 15 minutes and then check
that the CHARGE lamp on VF-AS1/PS1 is no longer lit.
(2) Securing the option to the inverter
a)
Insert a flat-blade screwdriver in each of the two holes at the upper part of the front
panel, release the panel mounting tab by pushing the screwdriver down and remove
the front panel cover.
b) Install the option in the inverter by fitting the tabs on the lower side the option into the
slots at the lower part of the inverter front panel.
*1
c) Make sure the option is securely attached to the inverter. Then check whether the
plastic bosses on the inverter case have fitted in the holes at the upper and lower
parts of the option.
d) Insert the tabs at the lower part of the front cover into the slots at the lower part of the
inverter to attach the front cover to the inverter.
*1
e) Stuck the enclosed "LED name label" in the option LED display part of a front cover.
b)
c)
e)
d)
LED name label
*When installing this option to below capacities,
remove the Add-on type option case.
VF-AS1: 200V 55, 75kW
400V 90 - 500kW
Connecter pin
Connecter pin
Port R
Port L
Link
NS
MS
VF-PS1: 200V 55KW - 90KW
400V 90 KW - 630KW
a)
*1: Do not bend the connect pins
when you install the option card or front panel.