ACCESSORIES
TMC7 Series
Page 18
710-02887-00A
Examples
Command: Start
Message
Starter
Address
Function
Code
Register
Address
Data
CRC
In 20 06 40002 1
CRC1,
CRC2
Out 20 06 40002 1 CRC1,
CRC2
Starter Status: TMC7 Running
Message
Starter
Address
Function
Code
Address /
Bytes Read
Number /
Value
CRC
In 20 03 40003 1
CRC1,
CRC2
Out
20
03
2
xxxx0011
CRC1, CRC2
Trip Code: Motor overload
Message
Starter
Address
Function
Code
Address /
Bytes Read
Number /
Value
CRC
In 20 03 40004 1
CRC1,
CRC2
5.4 Profibus
Module
Part Number: TMC7-PBM-01
The Profibus Module can be used with the TMC7 to enable control and monitoring via a Profibus network.
Adjustment Address
Data rate
The interface has data rate auto-detection so no adjustment is required for this
.
Low Voltage Switchgear (LVSG)
Motor Starter Format 1 Profile Basic Data Structure
Master > Slave Control Word is structured as follows.
BYTE 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved Reserved
Reserved
Reserved
Reset
Reserved
Reserved
Fwd
Run
BYTE 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved Reserved Reserved
Quick Stop
Reserved Reserved Reserved Reserved
Slave > Master Status Word is structured as follows.
BYTE 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved Reserved Reserved Reserved Reserved
Fault
On
Ready
BYTE 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Ramping
Reserved
Motor Current (% FLC)
1
1
Only available from TMC7 units with serial number format xxxxx-4 or greater.
ADDRESS
MSD
LSD