Toshiba TDDP2012ES2C Owner'S Manual & Installation Manual Download Page 10

Safety 

Precautions

 Page 10

 

 

 

 

 

    cylinders. (No more than 80 % volume liquid charge).     i)  Do not exceed the maximum working 
    pressure of thecylinder, even temporarily.     j)  When the cylinders have been filled correctly and the 
    process completed, make sure that the cylinders and the equipment are removed from site promptly 
    and all isolation valves on the equipment are closed off.     k) Recovered refrigerant shall not be charged 
    into another refrigeration  system unless it has been cleaned and checked.
15.Labelling
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The 
    label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment 
    contains flammable refrigerant.
16.Recovery
    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended 
    good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, 
    ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct 
    number of cylinders for holding the total system charge is available. All cylinders to be used are 
    designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the 
    recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 
    valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before 
    recovery occurs. The recovery equipment shall be in good working order with a set of instructions 
    concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. 
    In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall 
    be complete with leak-free disconnect couplings and in good condition. Before using the recovery 
    machine, check that it is in satisfactory working order, has been properly maintained and that any 
    associated electrical components are sealed to prevent ignition in the event of a refrigerant release. 
    Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier 
    in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants 
    in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, 
    ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant 
    does not remain within the lubricant. The evacuation process shall be carried out prior to returning the 
    compressor to the suppliers. Only electric heating to the compressor body shall be employed to 
    accelerate this process. When oil is drained from a system, it shall be carried out safely. 

Before carrying out this procedure, it is essential that the technician is completely familiar with the 
equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 
required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before 
the task is commenced. 

14.Decommissioning

a) Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before 
attempting the procedure ensure that: Mechanical handling equipment is available, if required, for 
handling refrigerant cylinders;All personal protective equipment is available and being used correctly; 
The recovery process is supervised at all times by a competent person; Recovery equipment and 
cylinders conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a 
vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the
system.     f) Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the 
recovery machine and operate in accordance with manufacturer's instructions.    h) Do not overfill 

Summary of Contents for TDDP2012ES2C

Page 1: ...DEHUMIDIFIER Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new machine Make sure to save this manual for future reference ...

Page 2: ...aintenance Table of Contents Control Panel Features 12 Other features 13 Removing the collected water 14 Clean the bucket 16 Troubleshooting Tips 17 Clean the air filter 16 Store the unit 16 Identification of parts 11 Design Notice 11 Positioning the unit 11 Troubleshooting Tips ...

Page 3: ... the unit Do not use the machine near flammable gas or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during operation Do not use the unit in small spaces Do not put in places where water may splash onto the unit Place the unit on a level sturdy section of the floor Do not cover the intake or exhaust openings w...

Page 4: ...en damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut off to avoid damage to the machine due to lightning Do not run cord under carpeting Do not cover cord with throw rugs runners or similar coverings Do not route cord under furniture or appliances Arrange cord away from traffic area and where it will not be tripped over Do not operate unit with...

Page 5: ...n of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehumidifier in the European countries the following information must be followed The municipality has established collection systems where electronic waste can be disposed of at least free of charge to ...

Page 6: ...enance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appliance shall be stored in a room without continuously operating open flames for example an operating gas appliance and ignition sources for example an operating electric heater Appliance should be installed operated and...

Page 7: ...mable material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants i e non sparking adequately sealed or intrinsically safe 5 Presence of fire extingu...

Page 8: ... supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation 2 Particular attention shall be paid to the following to en...

Page 9: ...tions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not...

Page 10: ...ng order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in...

Page 11: ...ns see the Remote Controller Instruction packed with the unit for details Design Notice In order to ensure the optimal performance of our products the design specifications of the unit are subject to change without prior notice Preparation 20cm or more 40cm or more 20cm or more 20cm or more 40cm or more This unit is designed to operate with a working environment between 5 C 41 F and 32 C 90 F and ...

Page 12: ...quel to or less than 0 C 32 F Comfort button On some models Press to activate the comfort dehumidifying operation At Comfort dehumidifying mode the unit will automatically control room humidity in a comfortable range 45 55 according to the room temperature The humidity setting function will be invalid Note On this operation the unit can not be set humidity level Continue CONT button On some models...

Page 13: ...ket is ready to be emptied or when the bucket is removed or not replaced in the proper position Auto Defrost When forst builds up on the evaporator coils the compressor will cycle off and the fan will continue to run until the frost disappears proper position When the setting humidity is reached the unit will be shut off automatically For some models the fan motor will continue to run for 30 secon...

Page 14: ...inage facility by attaching the pump drain out with a pump drain hose od Φ1 4 supplied 3 Pump draining on some models water outlet Note If the pump hose drops when you remove the bucket you must reinstall the pump hose properly to the unit before replace the bucket into the unit Pump hose drops Reinstall pump hose properly Drain hose AdaptorA Note Make sure the connection is tight and there is no ...

Page 15: ... the pump draining feature When the pump draining feature is not being used remove the pump drain hose from the outlet Press the pump drain hose outlet in and take the pump drain hose out from it Make sure do not let the water in the pump hose drip to the floor Note Make sure the connection is tight and there is no leak Lead the water hose to the floor drain or a suitable drainage facility the dra...

Page 16: ...ter at least every 30 days or more often if necessary Care and cleaning of the dehumidifier WARNING Turn the dehumidifier off and remove the plug from the wall outlet before cleaning When not using the unit for long time periods After turning off the unit wait one day before emptying the bucket Clean the main unit bucket and air filter Wrap the cord and bundle it with the band Cover the unit with ...

Page 17: ... dehumidifier has Auto defrost feature Did not allow enough time to remove the moisture Make sure there are no curtains blinds or furniture blocking the front or back of the dehumidifier The humidity control may not be set low enough Check that all doors windows and other openings are securely closed Room temperature is too low below 5 C 41 F There is a kerosene heater or something giving off wate...

Page 18: ......

Page 19: ......

Page 20: ... and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version ...

Page 21: ... 290 3 颜色 黑白 4 注意 排版时注意页码数字都是靠外面的 以便翻阅 5 装订 备注 1 基准说明书只适合K平台所有常规机型 2 基准说明书为单英文版本 不含型号及商标 也无制造商信息 请业务根据所 销售国家或者区域的法规要求 使用对应的官方语言版本 增加型号及其它 法规要求信息 重新申请订单编码说明书 3 基准说明书的显示标贴为K平台全功能 包含了目前已有的所有图标和功能按键及其 操作说明 4 后面的选配页面标明了对应的不同机型 可燃冷媒与非可燃冷媒 下要修改的内容 ...

Page 22: ...当机型为非可燃冷媒机型时 请进行以下变更 删除Pg6 Pg10 WARNING for Using R32 R290 Refrigerant 内容 ...

Reviews: