Location for Installation

WARNING

If the user inserts his finger or other object into the air outlet during the operation of the air conditioner, it may cause injury 
or electric shock. Therefore, please fit the air outlet at a distance of 2.5 m or more over the ground. 

In order to avoid incomplete combustion, do not place the combustion device at the air outlet.

Please fit the air outlet at a distance of 1.5 m or more from the fire alarm. Otherwise, in case of a fire, the fire alarm may be 
delayed or malfunction. 

Please ensure there are no obstacles around the air outlet.

Please install it directly below the air outlet where there are no obstacles such as decorative ceiling or curtain boxes. 
Otherwise, it may lead to obstacles and 3DW Diffusor condensation or dirt, and may affect the cooling and heating 
performance.

Please make sure both cold and warm air can circulate evenly in the location of installation. 

Installation under high humidity conditions

The product has passed the condensation test and is confirmed to be normal. However, water dripping may occur during 
continuous operation under high humidity conditions. Especially in the following installation places, it is possible to form 
high humidity air (dew point temperature above 23 °C).

1) A place near the window
2) A place near the entrance and exit door
3) Kitchen
4) A place where the 3DW Diffusor is exposed to the outdoor air directly

In the above places, please paste heat insulation materials such as sponges on the panel and the horizontal louver of 3DW 
Diffusor that are exposed to high humidity air.

[Reference] Test conditions for condensation

Indoor: Dry ball temperature 27 °C

Wet ball temperature 24 °C

Air volume: Low

Running time: 4 hours

7

Space for Installation

CAUTION

If the distance D between the indoor unit and the wall is less than 91 mm or greater than 1000 mm, this product cannot be 
applied.

Please ensure that the distance from the upper end of the 3DW Diffusor to the ceiling is more than 150 mm. Otherwise, 
there may be condensation or dirt on the ceiling.

*1:  If 91 < D ≤ 101, for the pasting method of heat insulation material, please refer to [Sticking sponge on mounting frame] in 

[8. Installation of 3DW Diffusor].

*2:  If 101 < D ≤ 1000, please purchase air ducts, installation wooden frame, and wooden screws locally.

PROHIBITION

Do not install the 3DW Diffusor upward and downward by the connecting air duct. Otherwise, dripping water and abnormal 
operation of horizontal louver may occur.

D (mm)

Connection mode

D < 91

Not applicable to this product

D = 91

Direct connection

91 < D ≤ 101

Direct connection (additional heat 

insulation material)

*1

101 < D ≤ 1000

Connecting air duct

*2

1000 < D 

Not applicable to this product

D

Wall

3DW Diffusor

Ceiling

More than

150 mm

Indoor unit

3DW Diffusor

3DW Diffusor

Air duct

Do not install upward

Indoor unit

Air duct

Indoor unit

Do not install downward

Summary of Contents for TCB-TDL0141SDY-E

Page 1: ...s Ελληνικα Svenska Suomi Norsk Dansk Română Български Eesti Latviski Slovenčina Slovenščina AIR CONDITIONER ACCESSORY Installation Manual 3DW Diffusor Model name TCB TDL0141SDY E TCB TDL0181SDY E TCB TDL0271SDY E TCB TDL0141SDY TR TCB TDL0181SDY TR TCB TDL0271SDY TR For commercial use Ticari kullanım için ...

Page 2: ...ctions may result in drop noise vibration water leakage and other problems Only a qualified installer or qualified service person is allowed to carry out the installation work Improper installation may result in water leakage electric shock fire and other problems Before the installation maintenance repair or removal work please set the circuit breaker to the OFF position otherwise there is a risk...

Page 3: ...ulation sponge Inside heat insulation for mounting frame 190 33 6 1 3 Fixing screw for mounting frame M4x8 16 9 Wire clip 1 10 Binding belt 2 4 Fixing screw for front panel assembly M4x25 6 11 Owner s manual 1 12 Installation manual this manual 1 4 Part Names 5 Dimension Unit mm Horizontal louver swing up and down Vertical louver swing left and right Panel 34 5 11 80 5 7 5 21 6 61 180 94 42 Distan...

Page 4: ...door 3 Kitchen 4 A place where the 3DW Diffusor is exposed to the outdoor air directly In the above places please paste heat insulation materials such as sponges on the panel and the horizontal louver of 3DW Diffusor that are exposed to high humidity air Reference Test conditions for condensation Indoor Dry ball temperature 27 C Wet ball temperature 24 C Air volume Low Running time 4 hours 7 Space...

Page 5: ... frame Only 12 places on TCB TDL0141SDY C need to be fixed meaning there will be 4 fixing screws for mounting frame 3 left 3 Fixing screw for mounting frame 2 Mounting frame Indoor unit Sticking sponge on mounting frame Please stick 2 pieces of sponge 5 and 2 pieces of sponge 6 that are attached with the machine to the fixed screws for mounting frame 3 Please stick the attached sponge 7 onto the a...

Page 6: ...g and fix the mounting frame with screws Please install the indoor unit and connect the pipelines Perform the heat insulation treatment on the refrigerant connecting pipe and drainage pipe For details refer to the installation manual of the indoor unit Please make the drill on the wall according to Drilling on the wall Please refer to the figure below to install the wooden frame locally purchased ...

Page 7: ...cting wire of the front panel assembly 1 to the wall opening and then push the front panel assembly 1 into the opening Temporarily fix two screws at the central part of the panel assembly 1 with the complimentary fixing screws for panel assembly M4x25 4 Similarly after temporarily fixing the remaining 4 screws tighten all the screws 6 in total Pay attention to the tightening sequence of the screws...

Page 8: ... drainpipe Side cover of PCB board Plug of PCB board Plug the connector of the wire into the PCB board socket CN510 white To protect the PCB board from the external pressure fix the connecting wire on a wire clip on the back of the side cover of the PCB board about 100 mm away from the plug with the binding belt 10 Close the side cover of the PCB board and fix it with 2 screws Tidy wires Tidy the ...

Page 9: ...l static pressure Please refer to the installation manual of indoor unit for the setting method of external static pressure The pressure loss characteristics of 3DW Diffusor will affect the external static pressure Please refer to the attached fan characteristics for details To avoid deviation from the operating range please adjust the air volume by adjusting the air doors set at the suction and a...

Page 10: ...door unit before the trial operation of the 3DW Diffusor For details refer to the installation manual of the indoor unit Please control the operation of the horizontal louver and vertical louver by the remote controller and confirm that the movement and sound are normal Refer to the manual of the remote controller for operation The clearance on the right side of the horizontal louver must be even ...

Page 11: ...35 200 300 400 500 600 700 Static Pressure Pa Blowing downward Blowing horizontally Low 20 Pa Low 10 Pa High 20 Pa High 10 Pa 0 5 10 15 20 25 30 35 40 400 500 600 700 800 900 1000 Static Pressure Pa Blowing downward Blowing horizontally Low 20 Pa Low 10 Pa High 20 Pa High 10 Pa 0 5 10 15 20 25 30 35 40 400 500 600 700 800 900 1000 Static Pressure Pa Blowing downward Blowing horizontally Low 20 Pa ...

Page 12: ...D0X7203601 00 ...

Reviews: