Location for Installation
WARNING
•
If the user inserts his finger or other object into the air outlet during the operation of the air conditioner, it may cause injury
or electric shock. Therefore, please fit the air outlet at a distance of 2.5 m or more over the ground.
•
In order to avoid incomplete combustion, do not place the combustion device at the air outlet.
•
Please fit the air outlet at a distance of 1.5 m or more from the fire alarm. Otherwise, in case of a fire, the fire alarm may be
delayed or malfunction.
•
Please ensure there are no obstacles around the air outlet.
•
Please install it directly below the air outlet where there are no obstacles such as decorative ceiling or curtain boxes.
Otherwise, it may lead to obstacles and 3DW Diffusor condensation or dirt, and may affect the cooling and heating
performance.
•
Please make sure both cold and warm air can circulate evenly in the location of installation.
•
Installation under high humidity conditions
The product has passed the condensation test and is confirmed to be normal. However, water dripping may occur during
continuous operation under high humidity conditions. Especially in the following installation places, it is possible to form
high humidity air (dew point temperature above 23 °C).
1) A place near the window
2) A place near the entrance and exit door
3) Kitchen
4) A place where the 3DW Diffusor is exposed to the outdoor air directly
In the above places, please paste heat insulation materials such as sponges on the panel and the horizontal louver of 3DW
Diffusor that are exposed to high humidity air.
[Reference] Test conditions for condensation
Indoor: Dry ball temperature 27 °C
Wet ball temperature 24 °C
Air volume: Low
Running time: 4 hours
7
Space for Installation
CAUTION
•
If the distance D between the indoor unit and the wall is less than 91 mm or greater than 1000 mm, this product cannot be
applied.
•
Please ensure that the distance from the upper end of the 3DW Diffusor to the ceiling is more than 150 mm. Otherwise,
there may be condensation or dirt on the ceiling.
*1: If 91 < D ≤ 101, for the pasting method of heat insulation material, please refer to [Sticking sponge on mounting frame] in
[8. Installation of 3DW Diffusor].
*2: If 101 < D ≤ 1000, please purchase air ducts, installation wooden frame, and wooden screws locally.
PROHIBITION
•
•
Do not install the 3DW Diffusor upward and downward by the connecting air duct. Otherwise, dripping water and abnormal
operation of horizontal louver may occur.
D (mm)
Connection mode
D < 91
Not applicable to this product
D = 91
Direct connection
91 < D ≤ 101
Direct connection (additional heat
insulation material)
*1
101 < D ≤ 1000
Connecting air duct
*2
1000 < D
Not applicable to this product
D
Wall
3DW Diffusor
Ceiling
More than
150 mm
Indoor unit
3DW Diffusor
3DW Diffusor
Air duct
Do not install upward
Indoor unit
Air duct
Indoor unit
Do not install downward