- 27
INTERFACE (cont’d)
Digital Input Descriptions **
Name
Description
B
Brake release command issued
1:Brake release sent, 0:Brake release not sent
(Use when open command sent by other equipment)
BA
Brake answer back
1: Brake is open, 0: Brake is closed
BC
Brake closed
1: Brake function normal, 0:Brake forced closed
BLA
Input breaker state
0:Breaker open, 1:Breaker closed (“a” aux contact)
BRTST
Brake test
1:Brake forced open, 0:Brake function normal
B_HLTY
Brake healthy
1:Healthy, 0:Not healthy
DIR0_DI
Direction select 0
DIR1_DI
Direction select 1
0:Forward, 1:Reverse
(Operates only when keypad is in remote mode.)
EXRST External
reset
1:External reset (Momentary input must be used)
0:No reset
EXT0
Two wire start/stop 0
1:Start, 0: Stop (Refer to SEL_DI)
EXT1
Two wire start/stop 1
1:Start, 0: Stop (Refer to SEL_DI)
EX_LMT_I1
Total output current limit selection
0:Use LMT_I1, 1:Use LMT_I1_EX
EX_LMT_TR
Torque reference limit selection
0:Use LMT_TRQ & LMT_TRQ_INV
1:Use LMT_TRQ_EX & LMT_TRQ_INV_EX
E_DRIVE
Drive emergency command
0:Normal operation, 1:Emergency operation
F
Forward jogging command
(F,R)=(1,0) :Forward jogging start
(F,R)=(0,0) :Forward jogging stop
(F,R)=(0,1) :Reverse jogging start
(F,R)=(0,0) :Reverse jogging start
(F,R)=(1,1) :First received jogging start
(EXT must be off)
R
Reverse jogging command
See above
FLD
Field current command
1:Field current on when READY
0:Field current off until start command received
F_LMT
Forward speed limit
1:Use LMT_SP_F, 0:Set forward speed limit to 0
R_LMT
Reverse speed limit
1:Use LMT_SP_R, 0:Set reverse speed limit to 0
HOLD
Emergency speed hold
0:Normal operation, 1:Maintain speed reference
IL Interlock
1:Interlock released, 0: Interlocked
LATCH_PG_POS Latch the PG/shaft position input
Stores the PG/shaft position at the time the input goes to
1in PG_POS_RLATCH and in PG_POS_FLATCH at the
time the input goes to 0.
MV_JOG_B3
Speed select bit 3
MV_JOG_B2
Speed select bit 2
MV_JOG_B1
Speed select bit 1
MV_JOG_B0
Speed select bit 0
(B3,B2,B1,B0)=(0000): Speed0 select
(B3,B2,B1,B0)=(0001): Speed1 select
(B3,B2,B1,B0)=(0010): Speed2 select
(B3,B2,B1,B0)=(0011): Speed3 select
(B3,B2,B1,B0)=(0100): Speed4 select
(B3,B2,B1,B0)=(0101): Speed5 select
(B3,B2,B1,B0)=(0110): Speed6 select
(B3,B2,B1,B0)=(0111): Speed7 select
(B3,B2,B1,B0)=(1000): Speed8 select
(B3,B2,B1,B0)=(1001): Speed9 select
(B3,B2,B1,B0)=(1010): Speed10 select
(B3,B2,B1,B0)=(1011): Speed11 select
(B3,B2,B1,B0)=(1100): Speed12 select
(B3,B2,B1,B0)=(1101): Speed13 select
(B3,B2,B1,B0)=(1110): Speed14 select
(B3,B2,B1,B0)=(1111): Speed15 select
(Used in conjunction with F and R inputs and CR_SP0-15)
M_FN
Motor cooling fan state
1:Cooling fan running, 0:Cooling fan stopped
OH_ACL
AC reactor overheat
1:Not overheated, 0:Overheated
Summary of Contents for T300MVi MEDIUM VOLTAGE
Page 18: ... xviii This page intentionally left blank ...
Page 85: ... 64 DRIVE INSTALLATION DRAWINGS cont d Frame G4P drive lifting and assembly ...
Page 86: ... 65 DRIVE INSTALLATION DRAWINGS cont d Frame G4P drive main cable installation ...
Page 87: ... 66 DRIVE INSTALLATION DRAWINGS cont d Frame G4P module lifting and installation D C B A ...
Page 89: ... 68 DRIVE INSTALLATION DRAWINGS cont d Frame H4P drive lifting and assembly ...
Page 90: ... 69 DRIVE INSTALLATION DRAWINGS cont d Frame H4P drive main cable installation ...
Page 91: ... 70 DRIVE INSTALLATION DRAWINGS cont d Frame H4P module lifting and installation ...