- 6
INSPECTIONS AND MAINTENANCE
(cont’d)
Parts to be Regularly Renewed
To use the T300MVi for a maximum period of time, it is necessary to regularly renew (replace)
components whose characteristics have deteriorated. The table below shows the parts used for the inverter
equipment whose regular renewal is recommended and their recommended renewal period.
Parts to be Regularly Renewed
Product name
Recommended
renewal period
Remarks
Cooling fan
3 years
Sooner if dust or dirt
damages bearings
Air filter
6 months
Can also be cleaned.
Aluminum Electrolytic
Capacitors
On Circuit Boards
7 years
Contact Toshiba for
replacement of these
devices
Oil-filled capacitor
Main circuit
20 years
Control power supply
7 years
Main circuit
7 years
Fuse
Control circuit
7 years