IF08CZ10 April, 2019
- 23 -
Item
Abbreviation
Hardware
Detection
Software
Detection
Heavy Fault
Medium
Fault
Light
Fault
Start
Interlock
Coast
to stop
Decel
stop
Stop
request
Alarm
Overload alarm
OL_A,OL_A_B
O O
Overload (5 minutes)
OL5, OL5_B
O O
Overload (20 minutes)
OL20, OL20_B
O O
Over speed
OSS
O O*
Output frequency high
OSS_F0
O O*
DC bus over-voltage positive/negative
OV_xP
OV_xN
O O*
Panel safety switch
P_SW
O
O
Emergency Stop by Keypad
DSP_ESTP
O
O
Parameter setting error
PARA_ERR
O O
PLL phase error
PHASE_ERR
O O
PLD error
PLD_ERR
O O*
Pre-charge CTT trip
PRE_CTT
O O
Pre-charge CTT alarm
PRE_CTT_F
O O O
DC Bus Charging Failure
REC_F
O
O
Rectifier failure
FUSE
O
O*
Reverse rotation failure
REV_ROT_F
O O*
Rotation/start failure
ROT_F
O O*
Soft stall
SOFT_STL
O
Analog Input Fault
AIN_FAULT
O O*
O
Speed feedback error
SP_ERR
O O*
Speed feedback error2
SP_ERR2
O O*
Speed reference lost
SP_LOST
O O
O
Speed reference lost alarm
SP_LST_A
O O O
Motor turning start interlock
SP_SIL
O
Spare input 1-4
SPA1-4
O O*
O
O
Spare input 1-4 timer
SPA1-4_T
O O*
O
O
System configuration error
SYS_ERR
O
O
Communication error 1-4
TL_F1-4
O O
O
Main under-voltage
UV_MPSF
O O
AC main voltage drop
UVA_SIL
DC under-voltage start interlock
UV_SIL
O O
O
DC under-voltage trip
UVD, UVD_B
O O
External equipment electrical ready condition
UVA_EX
O O
External safety switch
UVS
O
O
Input voltage phase loss
VAC_PH_LOSS
O O
Input Voltage Phase Rotation Error
VAC_ROT_F
O
O
Converter Input Phase Lost
VCNV_PH_LOSS
_
O O
Output current phase loss
VINV_PH_LOSS
O O
Inverter output voltage PLL error
VPLL_ERR_
O
O
Transfer Failure
XFR_FAIL
O
O
Transfer Incomplete Sequence
XFR_INCMP
O
Capture Failure
CPT_FAIL
O
Stator Over Voltage
OV_S
O
O*
Field Current Limit Timer
FCL_T
O
O*
Field Current Limit Timer Alarm
FCL_TA_
O
O
Exciter Failure (Exciter Detection)
FL_FAULT_
O
O*
Instantaneous Field Overcurrent (Exciter
Detection) FOC
O O*
Instantaneous Field Overcurrent
FOC_S
O
O*
Exciter Stopped while Running
FSTOP
O
O*
Field Current Lost
LF
O
O*
Limit Fault Reset
LMT_FRST
O
O*
(Note 1) Hardware Detection: Items for which all IGBTs are directly turned off by hardware. Software Detection: Items for which the
protective interlock operation is performed by detecting errors, via software.
(Note 2) "O" marks in the interlock operation fields can be selected by parameter setting.
"*" indicates that the equipment outputs the trip signal to the input main circuit breaker.
“x” indicates the phase (U,V,W).
Summary of Contents for T300MTX
Page 19: ...IF08CZ10 April 2019 xix This page intentionally left blank ...
Page 62: ...IF08CZ10 April 2019 40 CIRCUIT OPERATION cont d 6600V configuration ...
Page 78: ...IF08CZ10 April 2019 56 DRIVE INSTALLATION DRAWINGS Frame 0 drive lifting and assembly ...
Page 106: ...IF08CZ10 April 2019 84 DRIVE INSTALLATION DRAWINGS cont d Frame A2 drive lifting and assembly ...
Page 109: ...IF08CZ10 April 2019 87 DRIVE INSTALLATION DRAWINGS cont d Frame B2 drive lifting and assembly ...
Page 111: ...IF08CZ10 April 2019 89 DRIVE INSTALLATION DRAWINGS cont d Frame D2 drive lifting and assembly ...
Page 116: ...IF08CZ10 April 2019 94 DRIVE INSTALLATION DRAWINGS cont d Frame A4 drive lifting and assembly ...